OSHRC ALJ decision Docket 91-2277 Decided June 7, 1993 Citations vacated Judge Paul L. Brady

A.R. Contractors, Inc.

LP-gas traffic-protection citation vacated

Apply this to your situation

This order from 1993 bound only the parties to this case; it isn't precedent. Ezel answers your situation under the current OSHA standards and Commission precedent, with citations.

Currency note: this decision dates from 1993
The OSHA standards may have been amended, penalty amounts have been adjusted, and later Commission or court decisions may have changed the analysis since then. Treat this page as historical context, not current compliance advice. Verify the current standard before relying on any specific rule, threshold, or penalty mentioned here.
Final order, not Commission precedent
This decision by an OSHRC Administrative Law Judge became a final order of the Commission because no Commissioner directed review (29 U.S.C. § 661(j)). It binds the parties but is not binding precedent in other cases. The full text below is from the official OSHRC release.
About this page: The plain-English summary and decision snapshot below were written by Ezel based on the official OSHRC release. The full text is the Commission's own document.
Read the official release (oshrc.gov)

Plain-English summary

A.R. Contractors used two liquid-petroleum gas tanks to fuel roofing operations at a Florida commercial construction project. OSHA alleged that the tanks were exposed to possible damage from construction traffic without adequate precautions. The judge rejected the contractor's argument that the standard was unconstitutionally vague, finding that it gave fair notice that employers must protect LP-gas systems from vehicle damage. He nevertheless found no violation because the tanks were in a fenced construction-only area, marked with warnings, positioned near trailer wheels, accompanied by fire extinguishers and pennant flags, and guarded by an employee at all times. The citation was vacated.

Decision snapshot

  • Cited standard(s): 29 C.F.R. § 1910.110(d)(10)
  • Outcome: The sole citation was vacated.
  • Key point: A broadly worded standard requiring precautions against vehicle damage does not necessarily require fixed barriers when the employer proves that its combined site controls adequately protect the LP-gas system.

Full text (OSHRC public release)

                         UNITED STATES OF AMERICA

OCCUPATIONAL SAFETY AND HEALTH REVIEW CohdMISSION
One Lafayette Centm
1120 20th Street, N.W. - 9th Floor
Washington, DC 200384419

SECRETARY OF LABOR
Complainant,
v. OSHRC DOCKET
NO. 91-2277
A. R. CONTRACTORS,INC.
Respondent.

                NOTICE OF DOCKETING
          OF ADMINISTlMTIVE LAW JUDGE’S DECISION                      .
 The Administrative Law Judge’s Re ort in the above referenced case wa;s

docketed with the Commission on May 7 1993. The decision of the Judge
will become a final order of the Commiskon on June 7, 1993 unless a .
Commission member directs review of the decision on or before that date. ANY -
PARTY DESIRING REVIEW OF THE JUDGE’S DECISION BY THE -
COMMISSIONMUST FILE A PETITION FOR DISCRETIONARY REVIEW.
Any such tition should be received by the Executive Secre on or before
May 27, 1ge93 in order to ermit sufficient time for its review.T ee .
Commission Rule 91,29 8 .F.R. 2200.91.
All further pleadings or communications regarding this case shall be
addressed to:
Executive Secretary
Occupational Safety and Health .-
Review Commission
1825 K St. N.W., Room 401
Washington., D.C. 20006-1246
Petitioning parties shall also mail a copy to:
Daniel J. Mick, Esq.
Counsel for Regional Trial Liti ation
Office of the Solicitor, U.S. DO5
Room S4004
200 Constitution Avenue, N.W.
Washington, D.C. 20210
If a Direction for Review is issued by the Commission, then the Counsel for
Regional Trial Litigation will represent the Department of Labor. Any party
havmg questions about review rights may contact the Commission’s Executive
Secretary or call (202) 634-7950.
FOR THE CO

Date: May 7, 1993
DOCKET NO. 91-2277
NOTICE IS GIVEN TO TiIE FOLLOWING:

Daniel J. Mia m
Counsel for Re 'onal Trial Liti ation
Office.of the &citor, U.S. DO%
Room S4004
200 Constitution Ave., N.W.
Washington, D.C. 20210

Ms. Bobb e D. Spears
Re ‘onal Helicitor
O&e of the Solicitor, U.S. DOL
Suite 339
1371 Peachtree Street, N.E.
Atlanta, GA 30309

Ronald M. Gaswirth, Esquire
Lmi M. McNally, Esquire
Gardere & Wynne
3000 Thanks ving Tower
Dallas, TX -w2014761

Paul L. Brady
Administrative Law Jud e
Occupational Safety an B Health
Review Commissron
Room 240
1365 Peachtree Street, N.E.
Atlanta, GA 30309 3119

00018347526:04
SECRETARY OF LABOR,
Complainant

          v.                                         OSHRC     Docket No.: 91-227’7

A. R. CONTRACIYORS, INC.,
Respondent.

Appearances:

   Leslk John RodriguezEsquire
          oma of the solicitot
          u. so Dcp0ttment of Labor
          Atlanta,Georgia
                  For Complainant

Before: Administrative Law Judge Paul L Brady

                             DECISION AND ORDER

   This proceeding is brought pursuant to Section 10 of the Occupational safety and

Health Act of 1970 (Act) to contest a citation and proposed penalty issued by the Secretary
of Labor (Secretary). Respondent, A R. Contractors, Inc. (AR) is alleged to have violated
the standard at 29 C.F.R. Q 1910.1lO(d)(10) during construction of a building in Jacksonville,
-Florida.
The basic facts are not in dispute that AR was a roofing contractor in construction
of a commercial building in the Avenue Mall in Jacksonville. Also, that two w)-gallon
liquid petroleum (LP) gas tanks were located in front of the rear wheels of two tanker
trailers as depicted in Exhiiits C-3 and C-4. There were “propane gas” and “no smog”
decals on the tanks.
The me&ed Violation of 29 C.F.R. 6 1910~110(d~lO~
The standard which pertains to the storage and handling of LP gases states as follows:
When damage to L&Gas systems from vehictilar traffic is a possibility,
prcawtions against such damage shall be taken.
29 c.FeR. 5 1910.110(d)(l) provides in pertinent part as follows:
This paragraph applies specifically to systems utilizing Storage
containers othertbanthose constructed in accordanccwithDOTspe6ifications
0 00
systms is defined in l9lOolOO(A)(ll) as:
[AIn assembly of equipment consisting essentially of the container or
containers, major devices such as vaporizers, safety relief vahw, excess flow
valves, regulators, and piping connecting such park
The citation allegesthat precautions were not taken to prevent damage-to LP gas
systems fkom vehicular traffic: Two 500-gallon LP-gas tanh alongside the roam at%he
north end of the building.
Compliance officer John Ruggles conducted the inspection that gave rise to issuance
of the citation. He test&d that the L&gas system consisted of the two trailem that beid
hot tw and the two U-gas tanks that were heling them. The hot tar was pumped to t&
roof of the building for the roofers (Tr. 60). He stated the tanks had a capacity of
25~gallons and not NO-gallons (Tr. 126).
The Secretary concedes the tanks were located in a fenced-off area restricted to
.
constiwtion trafk, and some colored flags were stmng between the trailers. -
Ruggks stated, however, that the L&gas tanks were located on the roadway side of
the trailers without protection from vehicular traffic (Tr. 61,62, 126; Exhs. C-3, C-4). He
observed vehicular tra!Sc within 3 to 4 feet of the tanks traveling 5 to 10 miles per hour. *
Three to five vehicles passed the banks during the inspection. The roadway was
approximate 20 feet side (Tr. 63-65).
Mr. Harold Blanton, the Secretary’s expert, testified that barriers should have been
present to prevent vehicle damage to the tanks (Tr. 183,184). He also stated that stringing
colored flags in front of the tar&s was not a precaution because of the vehicular traffic that
was present (Tr. 193495).

                                          2

In order to establish a violation of the standard, the Secretary must show by a
preponderance of the evidence that (1) the cited standard applied, (2) its term were not
met, (3) eapbyees had access to the violative condition, a;nd (4) the employer knew or
could bait kww of the violation with the exercise of reasoriable diligence. S&e2 Mb&
AU!‘& We Cqp, 15 BNA OSHC 1218,199l CCH OSHD 129,442, p. 39,678 (No. 88-
821,199l)m
AR contends the standard does not apply because of its vagueness thus violating the
due process clause of the fifth amendment. It is argued that the standard is void since
persons %f commonintelligence must guess at its meaning and differ as to its application.”
cbu8eQ v. Gene& cbnstr. coo, 269 us. 385,391(1926).
AR points out that the term “precautions” is not defined by the stx@ard. As a
result, the Secretary’s position is based solely on the subjective interpretations of the
inspectingoffice~
While the testimony of the compliance officer and expert does indicate that the
precaution to be taken are essentially lefk up to an inspector, the -standard is not
impermi6sib~vague.
. The standard does set fortha “Comprehens~We CCNUSC of amduct” that
satisfies due process requirements, ia, that employers are to protect IT-gas systems fkom’

            The fact -that Congress might, without difficulty, have chosen “[cjlearer
      and more precise language equally capable of achieving the end which it
                                                                                                .
      sought does not mean that the statute which it in fact drafkd is
      unconstitutionally va;uc. UitiM S&m v. Powell, 423 U.S. s% SAX 316
      (1975).
  Although a definition for precautions is not provided, its general definition would

include measures taken in advance to protect against danger. The standard is not
unconstitutionally vague to apply in this case and AR’s motion for summary judgment is
denied.
AR also contends that the evidence does not establish the violation. It is first
asserted that the tanks in question were not shown to be “other than DOT containers.”

                                           3

There is considera& evidence and discussion in the rexord regardingsp&&
identification of the tar&s shown in Exhl%itsc-3 and c-4. The testimony of two witnesses,
however, adequatelyestab@hes they were “other than D.O.T. containers.”
Mr.JatpB Hollinth, records custodian for GrifEthGas Company, testifkd his
company leased the tanks in question to AR (‘I?. 29-3237). Hollingswortbhas 20 years
experience with-the propane gas industry, from home delivery to basic service and
installation(Tr. 28). Based on his 20 years experience it was his opinionthat the tanks-were
ASME (American Societyof Mechanic& Engineers) tanks and not D.O.T. (Tr. 37,396o).
Harold Blanton, the Secretary’sexpert, identified the tanks a “non-D.O.TP but
ASME (Tr. 174,197). There was no evidence offered to refute the foregoingstatements.
The tanks, therefore, were “other than DOT containers.”
The testimonyof the inspectoris not disputed regardingAR’s LP gas system at the
site (Tr. 6041). Tberefore,an LP gas system was present within the contextoftbe standard
The centralissue regarding the allegedviolation relates to the extendof the measures ’
required to be taken by an employer under the standard CIearly, the employer has a duty
to act where there ida possibilityof damage to the system by vehicuk trafIic, “P-Ii
is used in the standard without qualification, wbicb implies even tbe sligbtest chance of
damage. The .testimony is undisputed that there was vehicular traffic traveling at speeds of
5 to 10 miles per hour within 3 to 8 feet of tanks. Under these circumstances, damage to
the gas system could be deemed a possibility. The standard also does not provide any
indication as to fype of precautions necessary to compIy. Consideration, therefore; must be
given to measures which are barely suffkient to protect against damage.
Mr. Blanton testified that in this case a barricade or barrier between the tanks and
trafk would be required. It is argued that such requirement is reasonable in light of other
prwisions of 29 CFR 8 1910.110. These provisions relate to precautions agabt vehicular
damage to LP gas tanks at gas setice stations. 29 C.F.R. 0 1910.110@)(6)(ii)@) provides
that above groundcontainersmust be “protected by crash rails or guards to prevent physical
damage unless they are protected by virtue of their location.” Under 29 CF.R. 9
1910.110@)(6)(iii)(c), “[i]f the location is subjected to vehicular traffic, containers shall be

                                          4

.
protected by a concrete slab or other cover adequate to prevent the weight of a Iadd
v&j& imposing comcntrated loads on the container shell.”
T~C~~IUGSS~~II has held that broad terms in a standard can acquire meaning when
read tagettWa.witbother standards. See Sccrcr~ry
v. Gocdm Inc., 7 BNA OSHC 1855,
1861, 1980 CCH OSHD 1 24,205, p. 29,444 (No. 76-2049, 1979). Since barriers and
barricades are not listed as precautions under the instant standard and there is no reason
to conclude such installationwould be required. Cleariy, if such measures were intendedthe
standard would so specify as set forth in the aforementioned standards. The principal
consideration, therefore, is what precautions AR did take. .
Mr. Duane Hughey, AR foreman, testified he was in charge of safety at the w&site.
He stated different precautions are taken at each worksite depending_on
. the circums~
and conditions. Based upon the conditions at this site, he took the fobwing prccautims
(Exhs. C-3, C-4; Tr. 26W63):
(1) The stringing of colored pennant flags between the tanker trail&,
(2) Fencing off the area and restricting it to const~ctim trafik, .
(3) Placingdecals on the tanks which read, “Propane Gas” an@“No Smoking,,”
(4) Positioningthe tanks in fkontof the rear wheels of the tankers,
(5) . Fire extinguishes were placed beside each tank, and
(6) Stationing a man to guard the tanks at all times.
While some of the measures may be seen as having minimal effect, when coupled
with the presence of an employee to guard the tanks full time, which is not refuted,
’ compliance with the standard cannot be denied. The standard was not violated as alleged.

                 FINDINGS OF FAa         AND CONCLUSIONSOF IAW


        The foregoing decision constitutes   the findings of fact and conclusions of law in
 accordance with Federal Rule of Civil Procedure 52(a).

ORDER

  Based on the foregoing decision, it is ordered that the citation is vacated.