🧪 TEST MODE ACTIVE Use test card: 4242 4242 4242 4242
OSHRC ALJ decision Docket 09-2035 Decided July 27, 2011 Mixed result Judge John H. Schumacher

O'Connell Electric Company, Inc.

PPE selection and hazard-certification items affirmed

Apply this to your situation

This order from 2011 bound only the parties to this case; it isn't precedent. Ezel answers your situation under the current OSHA standards and Commission precedent, with citations.

Currency note: this decision dates from 2011
The OSHA standards may have been amended, penalty amounts have been adjusted, and later Commission or court decisions may have changed the analysis since then. Treat this page as historical context, not current compliance advice. Verify the current standard before relying on any specific rule, threshold, or penalty mentioned here.
Final order, not Commission precedent
This decision by an OSHRC Administrative Law Judge became a final order of the Commission because no Commissioner directed review (29 U.S.C. § 661(j)). It binds the parties but is not binding precedent in other cases. The full text below is from the official OSHRC release.
About this page: The plain-English summary and decision snapshot below were written by Ezel based on the official OSHRC release. The full text is the Commission's own document.
Read the official release (oshrc.gov)

Plain-English summary

O'Connell Electric crews performed electrical replacement and maintenance work at a university building where some 34,500-volt switches remained energized. An electrician entered an energized switch cabinet outside the crew's assigned work and suffered severe burns in an arc flash. The judge found the vault crew qualified for an exclusion from several electrical work-practice standards. Even so, O'Connell violated general PPE standards by telling employees only to wear appropriate equipment instead of selecting and communicating the required protection, and one employee's gloves were inadequate for the thermal hazard. The company also failed to prepare the required written certification of its hazard assessment, though that item was classified as other than serious. Five other work-practice, eye-protection, warning-tag, training, and lockout items were vacated. The affirmed items carried total penalties of $13,230.

Decision snapshot

  • Cited standard(s): 29 C.F.R. § 1910.132(d)(1)(ii); 29 C.F.R. § 1910.132(d)(2); 29 C.F.R. § 1910.269(l)(2); 29 C.F.R. § 1910.138(a); 29 C.F.R. § 1910.133(a)(1); 29 C.F.R. § 1926.21(b)(2); 29 C.F.R. § 1926.417(b); 29 C.F.R. § 1910.145(f)(3)
  • Outcome: Two serious PPE items and one other-than-serious certification item were affirmed; five items were vacated; total penalties were $13,230.
  • Key point: An employer must make and communicate PPE selections and document its hazard assessment, even when experienced electricians are qualified to perform the work.

Full text (OSHRC public release)

                     United States of America
OCCUPATIONAL SAFETY AND HEALTH REVIEW COMMISSION
                1120 20th Street, N.W., Ninth Floor
                   Washington, DC 20036-3457

SECRETARY OF LABOR, :
:
Complainant, :
:
v. : OSHRC DOCKET NO. 09-2035
:
O‟CONNELL ELECTRIC COMPANY, :
INC. :
Respondent. :


APPEARANCES: Terrence Duncan, Esquire Thomas A. DeSimon, Esquire
Office of the Solicitor Steven P. Nonkes, Esquire
U.S. Department of Labor Harris Beach, PLLC
201 Varick Street 99 Garnsey Road
Suite 983 Pittsford, New York 14534
New York, New York 10014 For the Respondent
For the Complainant

BEFORE: John H. Schumacher,
Administrative Law Judge

                               DECISION AND ORDER

    This proceeding arises under the Occupational Safety and Health Act of 1970, as

amended, 29 U.S.C. § 651 et seq. (“the Act”). Following an accident at a worksite at the State
University of New York at Buffalo, Amherst Campus (“SUNY”), the Secretary issued a citation
to O‟Connell Electric Co., (“O‟Connell” or “respondent”) alleging several serious violations of
the Act. Respondent filed a timely Notice of Contest pursuant to section 10(c) of the Act,
bringing this matter before the Occupational Safety and Health Review Commission (“the
Commission”). After filing her initial complaint, the Secretary filed an amended complaint
alleging eight serious violations of the Act and proposing total penalties of $50,400. Respondent
filed its timely Answer and a hearing was held in Buffalo, New York from October 18-20, 2010.
Both parties have filed post-hearing briefs and this matter is ready for disposition.

                                   BACKGROUND
   Beginning on May 15, 2009, SUNY planned a scheduled electrical shutdown so it could

remove and replace metal clad switchgear in the “Adjacent Room” located in the basement of
Baldy Hall, a facility which also housed classrooms (Tr. 36-37). O‟Connell was hired to remove
all the switching gear in the in the Adjacent Room. This required removal of all the wiring and
conduits, the disconnection of bus ducts, its replacement with new equipment, and eventually the
reconnection of all the wiring, conduit and bus ducts (Tr. 37). Because the work required an
electrical shutdown, SUNY decided to add a preventive maintenance project on the switches and
transformers located in the Vault Room, which was also located in the basement of Baldy Hall.
Both rooms shared a common doorway which facilitated travel between them (Tr. 36).
The equipment in the Baldy Hall “Vault Room” is part of the SUNY Buffalo Campus
Utility System (Tr. 451). Electrical power is provided by a private utility company and the
SUNY Buffalo Campus Utility System distributes this power to various buildings on the campus.
(Tr. 447-448). The Vault Room contains two circuits, 53A and 25B. Circuit 25B is fed through
switches S1 and S4, while circuit 53A is fed through switches S2 and S3. The University did not
want a total electrical shutdown and therefore required that circuit 25B remain energized. (Tr. 51,
86-87). Therefore, only switches S2 and S3 were de-energized and these were the only switches
that employees were authorized to work on during the day in question.
On May 16, 2009, before the O‟Connell crews arrived, the utility company opened the
53A switch in nearby O‟Brian Hall, which fed electricity to Baldy Hall, so O‟Connell could
perform its work. The utility placed their locks and isolation devices on the switches. However,
they gave O‟Connell no guarantees regarding the de-energized status of any of the switches,
which meant that O‟Connell had to test the circuits and switches to determine their safety (Tr.
376-377, 379). In order to re-energize the 53A switches, the University would have to remove its
lock and keys. The actual re-energizing would be performed by the University (Tr. 377-378).

                                   The Adjacent Room
   The switchgear in the Adjacent Room was housed in large metal cabinets where they

                                              2

were attached to “bus ducts” that fed them the electricity that powered the switchgear (Tr. 151-
152, 161). These bus ducts ran from the Vault Room to the Adjacent Room and powered the
switches and transformers in both rooms (Tr. 151). In order to remove and replace the
switchgear, respondent had to remove all of the wiring, pipes and conduits that formed the core
and disconnect the switchgear from the bus ducts in the ceiling (Tr. 37, 135-138).
O‟Connell hired a rigging company to remove the metal cabinets and the old switchgear
out of the Adjacent Room and transport the new cabinets and switchgear into the room (Tr. 367).
The backup feed from nearby O‟Brian Hall to the Adjacent Room was deactivated and
the switch in O‟Brian Hall where it was deactivated was locked and tagged before the crew
arrived at the site on May 16, 2009 (Tr. 87, 339-340). Grounds were installed on the downstream
side of the switch where the backup feed was deactivated (Tr. 87, 339).
After the sources of electrical power were locked out and tagged and the grounds
installed, the busses and bus ducts running from the transformers in the Vault Room to the
switchgear in the Adjacent Room were disconnected from the switchgear in the Adjacent Room
and were dismantled (Tr. 154, 158, 171). The busses and bus ducts running from the backup feed
in O‟Brian Hall to the switchgear in the Adjacent Room were also disconnected from the
switchgear in the Adjacent Room and were dismantled (Tr. 154-155). The disassembly of busses
and bus ducts was completed before either the Adjacent Room crew or the Vault Room crew
arrived on the site on May 16, 2009 (Tr. 135, 171). The members of the Adjacent Room crew
could see that these busses were disconnected and suspended from the ceiling (Tr. 137, 154-155).
Four employees were assigned to work in the Adjacent Room: Roman Solecki, Kevin
Bacon, Jim Fleck and Mike Reynolds. These employees reported for work on 5:00 a.m. on
Saturday, May 16, 2009 (Tr. 38). Before they began work, O‟Connell foreman, Kevin Schoenthal
held a safety meeting with the crew (Tr. 38, 141). The meeting lasted between 15 minutes and
half an hour and covered thirteen topics listed on O‟Connell‟s Safety Meeting Sheet (Tr. 38, Ex.
P-011, Ex. P-023, p.10). Among the topics discussed were switching, testing and grounding
procedures, appropriate equipment needed for the tasks, personal protective equipment (“PPE”),
and a reminder that everyone was responsible for testing all equipment before they made contact
themselves, even if the equipment was previously tested (Ex. P-011). As part of the safety
meeting, Schoenthal took the Adjacent Room crew on a tour of the Vault Room (Tr. 319). The
purpose of the tour was to show the employees where all the equipment was de-energized, and

                                            3

where it was locked out for the project (Tr. 38). At the conclusion of the meeting, the Adjacent
Room crew signed the Safety Meeting Sheet as proof of their attendance (Tr. 230).
Foreman Schoenthal instructed Kevin Bacon to test the equipment in the Adjacent Room
before the crew started their shift because he was concerned about a potential electrical feedback
from another part of the building traveling into and affecting equipment in the Adjacent Room
(Tr. 137).
With the old equipment disconnected from all sources of electrical power, the Adjacent
Room crew proceeded to completely disassemble the old switchgear and began assembly of the
new switchgear (Tr. 199-202). However, at no time during the Adjacent Room crew‟s shift on
May 16, 2009 were the busses that supplied power to the switchgear in the Adjacent Room
reconnected (Tr. 141, 171). Therefore, throughout the shift, the switchgear remained de-
energized. Moreover, without being reconnected to the busses, the switchgear could not become
energized as the result of the actuation of a de-energizing point, such as the de-energized circuits
in the Vault Room, or the switch in O‟Brian Hall that deactivated the 53A circuits.
After the safety meeting ended, Schoenthal introduced a group lockbox for the crews of
both the Adjacent Room and the Vault Room (Tr. 53, 263, 291, 309, 317, Ex. P-23, p.8). Under
the group lockbox procedure, the Yale key that opened all the doors to cabinets S1-S4 and
transformers 1 and 2 in the Vault Room was placed in a box. Each employee would then put his
lock on the outside of the box. As a result, the box could not be opened until every employee
removed his personal lock (Tr. 284, 330). The procedure was not made mandatory. Therefore,
some of the employees did not place their lock on the group lockbox (Tr. 128, 138, 284).
Moreover, at some point, foreman Schoenthal took the Yale key out of the lockbox and handed it
to a member of the Vault Room crew (Tr. 333).
The key remained out of the box until the accident occurred (Tr. 333). However,
Schoenthal also instituted a mandatory sign-in/sign-out sheet (Tr. 68, 171-172, ) Under this
procedure, each employee signs out to verify that he is clear of the site and that all his tools and
personal effects have been removed (Tr. 119-120, 132, 171, 179, 237, 273, 348). Until all the
crew members have signed out, the system could not be re-energized (Tr. 347-348).

                                   The Vault Room
   The preventative maintenance project in the Vault Room on May 16 involved cleaning,

                                              4

lubricating, inspecting and testing two of the four switches (S2 and S3) and the two transformers
(T1 and T2) to ensure that they were in safe operating condition (Tr. 39). There were four
switches in the Vault Room that were housed in similar looking cabinets (Tr. 40, 179, Exs. RX
24-26). Just above the access handle of the outer door of each cabinet was a sign with a red
background that read “Danger High Voltage.” Behind the outer door of each metal cabinet was
an inner door through which one could see the switchgear. There was a warning sign on each of
those inner doors (Tr. 369-371).
These warning signs appeared on the outer and inner doors of each of the cabinets,
whether they were energized or not (Tr. 369-371). The Yale key, that was supposed to be placed
in the group lockbox, opened the door to each of the four cabinets and the two transformers (Tr.
48-49, 94-95, 335). The key did not control the energizing or de-energizing of any switch.
Rather, it only allowed the outer door each of the switches to be opened (Tr. 358). The four
switches were followed by the two transformers which also stood next to each other (Tr. 48-49,
94-95, 335, Ex. RX-27).
To maintain power to the other buildings on the campus, switches S1 and S4 remained
energized at 34,500 volts (34.5 KV)(Tr. 51, Ex. P-23, p.3). As a result, the employees worked on
switches S2 and S3 (circuit 53A), which were in the middle of the row of four switches, while
the two end switches (S1 and S4, circuits 25B) remained energized (Tr. 232-233, 246-247, 278,
299-300, 334). The Vault Room crew was instructed to work only on switches S2 and S3 (Tr.
303, 346-347).
Four employees were assigned to work in the Vault Room: [redacted], Jeff Wozniak,
James Woodfield and Keith Pastuszynski (Tr. 40-41). These employees started working at
approximately 7:00 a.m. on May 16, 2009 (Tr. 41). As with the Adjacent Room crew, foreman
Schoenthal held a safety meeting with the Vault Room crew before the start of their shift (Tr. 41,
348). After the meeting, Schoenthal took the crew on a tour of Baldy and O‟Brian Halls. He
showed them the equipment he had grounded and locked on (Tr. 124, 246). The purpose of the
tour was to show everyone that the switches on the equipment they were to work on were opened
and de-energized (Tr. 246, 250-251).
During the meeting, Schoenthal removed his locks and tags from switch cabinets S2 and
S3, the switches that the employees were scheduled to work upon (Tr. 356). Before the crew
began its work, Woodfield put on the PPE that he kept in his car and tested one of the de-

                                            5

energized 53A switches to verify that it was de-energized. Woodfield performed his task using a
12-inch long proximity voltage detector attached to the end of a six-foot long nonconductive “hot
stick” (Tr. 297). The testing confirmed that no voltage was present (Tr. 242). Woodfield then
applied protective grounds to each of the three phases on the line and the load sides of the
switches (Tr. 45, 239). Upon completion of the work on S3, the crew removed the grounds and
closed the cabinet (Ex. P-28). They then placed grounds on the switch in cabinet S2 (Tr. 48-49,
Ex. P-28-P-29). The crew then broke for lunch.

                                   The Accident
   After lunch, when work on S2 was complete, [redacted] and Wozniak removed the

grounds from S2 and closed its cabinet (Tr. 362, Exs. P-28, 29). [redacted] was in front of S2
picking up his tools, while Wozniak went to one of the transformers to assist Pastuszynski and
Woodfield with maintenance tasks (Ex. P-28). Foreman Schoenthal was summoned to address a
problem that occurred with the transformer. The door to the transformer was open, obscuring the
view of [redacted] from the rest of the crew (Ex. P-28).
For some unknown reason, [redacted] opened the door to and entered S4, a 25B switch,
which was not within the Vault Room crew‟s scope of work. An arc-flash occurred, knocking
[redacted] five feet across the room. He suffered a two-to-three inch laceration to the back of his
head and second and third degree burns to his face, shoulders, neck, torso, arms and hands. His
co-workers put out the fire that engulfed him and summoned emergency personnel who
transported him to a local hospital. In the rescue, Woodfield suffered burns on his left arm, but
refused treatment (Exs. P-16, P-28).
O‟Connell undertook an internal investigation of the accident. It concluded that
Schoenthal did nothing that contributed to the accident. It also concluded that [redacted] was
solely responsible for the accident, and he was subsequently disciplined (Tr. 176-177, Ex. P-35).

                                   DISCUSSION
   In her amended complaint, the Secretary alleges eight individual violations of the Act.

Retaining the numbering from the original citation, the remaining items may be grouped into
several general categories: PPE (items 2, 5 and 8); work practices and warning signs (items 4b,
13); Lockout/Tagout (“LOTO”) (items 11, 12); and workplace hazard assessment (item 3).

                                             6

Although the citation did not group the items by topic, they will be so analyzed here, rather than
in numerical order.
I. Applicability of the Standards at §§1910.331 through 1910.335.
To establish a violation of an OSHA standard, the Secretary must establish that: (1) the
standard applies to the facts; (2) the employer failed to comply with the terms of that standard;
(3) employees had access to the hazard covered by the standard, and (4) the employer knew or
could have known of the existence of the hazard with the exercise of reasonable diligence.
Atlantic Battery Co.,16 BNA OSHC 2131, 2138 (No. 90-1747, 1994).
As a preliminary matter, the Secretary alleged various violations of standards found at
29 C.F.R. §§1910.331 through 1910.335 (Items 4b, 8, 3, 13). O‟Connell raises issues regarding
the applicability of those standards. Although the Secretary, in her amended complaint, pled
violations of alternative standards for each of these violations, issues regarding the applicability
of §§1910.331 through 1910.335 run as a common thread throughout this case. Rather than
revisit the issue for each of the four relevant items, the matter will be resolved here.
Subpart S sets forth specific standards applicable to electrical work. Within Subpart S
the standards at §§1910.331 through 1910.335 set forth “Safety-Related Work Practices.”
However, §1910.331(c)(1) states:
(c) Excluded work by qualified persons. The provisions of §§ 1910.331 through
1910.335 do not apply to work performed by qualified persons on or directly
associated with the following installations:
(1) Generation, transmission, and distribution installations.
Installations for the generation, control, transformation, transmission,
and distribution of electric energy (including communication and
metering) located in buildings used for such purposes or located
outdoors.

      O‟Connell argues that this exemption applies to the crew that was working in the Vault

Room. First, it alleges that the Vault Room crew were all “qualified persons” within the meaning
of the standard. Second, it argues that the Vault Room qualified as a building and was used for
the transmission and distribution of electrical energy.
The Secretary claims that the exemption is not applicable on three grounds:
(1) The employees‟ failure to conduct an arc hazard analysis and their failure to wear appropriate
PPE demonstrates that they were not “qualified persons;”

                                              7

(2) The facility was not a facility for the “generation, control…and distribution of electric
energy;” and
(3) The exclusion applies only to work “on or directly associated with” generation, transmission,
distribution, and transformation equipment, and that the Vault Room crew was engaged only in
“routine maintenance.”
A. Qualified Persons
The Secretary asserts that Woodfield was not a qualified person because (1) he failed to
conduct an arc flash hazard analysis and denied that one was necessary; and (2) he did not know
what appropriate PPE he needed to wear.
1910.399 defines a “qualified person” as:

   One who has received training in and has demonstrated skills and knowledge in
   the construction and operation of electric equipment and installations and the
   hazards involved.

     Note 1 to the definition of “qualified person” states:

   Whether an employee is considered to be a “qualified person'' will depend upon
   various circumstances in the workplace. For example, it is possible and,
   in fact, likely for an individual to be considered “qualified” with regard to
   certain equipment in the workplace, but “unqualified” as to other equipment. (See
   1910.332(b)(3) for training requirements that specifically apply to qualified
   persons.)

      Note 2 to the definition of “qualified person” states:

    An employee who is undergoing on-the-job training and who, in the course of
   such training, has demonstrated an ability to perform duties safely at his or her
   level of training and who is under the direct supervision of a qualified person is
   considered to be a qualified person for the performance of those duties.

           1910.332(b)(3) further defines a “qualified person” as:

      Additional requirements for qualified persons. Qualified persons
     (i.e., those permitted to work on or near exposed energized parts)
     shall, at a minimum, be trained in and familiar with the following:
                (i) The skills and techniques necessary to distinguish exposed live
     parts from other parts of electric equipment,
                (ii) The skills and techniques necessary to determine the nominal
     voltage of exposed live parts, and
                (iii) The clearance distances specified in Sec. 1910.333(c) and the
     corresponding voltages to which the qualified person will be exposed.

                                             8

Note 1: For the purposes of Sec. Sec. 1910.331 through 1910.335, a
person must have the training required by paragraph (b)(3) of this
section in order to be considered a qualified person.

         Note 2: Qualified persons whose work on energized equipment involves
         either direct contact or contact by means of tools or materials must
         also have the training needed to meet Sec. 1910.333(c)(2).

The additional factor set forth in 1910.333(c)(2) provides:
(2) Work on energized equipment. Only qualified persons may work on
electric circuit parts or equipment that have not been deenergized under
the procedures of paragraph (b) of this section. Such persons shall be
capable of working safely on energized circuits and shall be familiar
with the proper use of special precautionary techniques, personal
protective equipment, insulating and shielding materials, and insulated
tools.

   I find that the crew working in the Vault Room met the requirements to be “qualified”

persons within the meaning of the above standards. Woodfield has been a licensed and certified
Master Electrician since 1994 (Tr. 216). To earn that designation, he had to pass a test that
proved he had the ability to do the work completely (Tr. 216). Prior to that, he completed an
apprenticeship program with the International Brotherhood of Electrical Workers (IBEW) in
1994 (Tr. 217). He received on the job training for the last 3 years with O‟Connell (Tr. 218). He
continued to receive training after receiving his master status. He has had arc class training (Tr.
219) and has had several jobs in de-energized maintenance and high voltage experience (Tr. 220-
221, Ex. RX-5, Ex RX-6). He took the OSHA 10-hour course twice; once as a journeyman and
once as an apprentice (Tr. 223). He has worked on at least nine jobs where did de-energized
shutdowns which involved the same kinds of tasks at Baldy Hall (Tr. 224). There were another
ten times where he was hired to verify that new equipment was operating correctly and to test
vaults in order to put them into service for the transmission and distribution of electrical power
(Tr. 225). At the time of this incident, Woodfield had been working with electricity for 24 years
(Tr. 223).
The Secretary‟s argument that Woodfield‟s failure to conduct an arc-flash analysis and
the improper use of PPE disqualifies him from “qualified person” status, essentially implies that
whenever an electrician does anything contrary to code/accepted procedure ipso facto establishes

                                               9

that he is not a “qualified person.” This overlooks the simple truth that well-trained and
competent employees will occasionally err, be it the result of laziness, mistake, inadvertence, or
shortcut. The record establishes that Woodfield is a well-trained and highly experienced Master
Electrician with a good comprehension of arc-flash analysis (Tr. 209-211). Therefore, I find that
Woodfield was a “qualified person.”
Similarly, I find that the other crew members of the Vault Room crew to be “qualified
persons.”

Jeff Wozniak
Jeff Wozniak has been working as an electrician for 21 years (Tr. 268). He completed his
apprenticeship training program and is now a journeyman electrician (Tr. 267, 268, Ex. 44 p. 13).
Being a journeyman means that the person completed training and is qualified to do electrical
work. He has taken the OSHA 10-hour and 30-hour courses and receives training on a monthly
basis (Tr. 278). Wozniak also took an electrical safety and maintenance seminar in Auburn NY in
January 2009 (Tr. 280).

Keith Pastuszynski
Keith Pastuszynski has been doing electrical work for 13 years (Tr. 296). He began
working for O‟Connell in 2005 and completed his 5-year apprenticeship program in 2007 (Tr.
287, 295-296, Ex. RX45, pp. 2-3) and is now a journeyman electrician (Tr. 337). He has taken
the OSHA 10-hour training course, and has been trained in relay maintenance for electro-
mechanicals and microprocessor based relays and ground testing. He has also taken seminars in
Lockout/Tagout (“LOTO”) and arc-flash (Tr. 297).

Kevin Schoenthal
Foreman Kevin Schoenthal has been employed by O‟Connell since 1999. Prior to that, he
was employed by Industrial Power & Lighting since 1992. He completed the 5-year
apprenticeship program, is a journeyman electrician (Tr. 336, 337, (Ex. 45 pp. 4-5) and is
considered by O‟Connell to be one of their qualified people (Tr. 366).

                                            10

[redacted]
[redacted] is qualified as a journeyman electrician (Tr. 183, Ex. RX-9). He completed
substation safety training through Rochester Gas and Electric, permitting him to work unattended
in substations (Tr. 183). He completed de-energized maintenance and arc-flash training (Tr. 183).
He is also AEMC Ground Testing Certified and is a TEGG-Certified Technician (Ex. RX-9, 10).
[redacted] completed the OSHA 10-hour training course in Construction Safety and Health (Ex.
RX-11).
Having reviewed the credentials of the Vault Room crew and, except for [redacted],
having had the opportunity to hear and assess their testimony, I conclude that, by way of training
and experience, the Vault Room crew were all “qualified persons” within the meaning of Subpart
S.
B. Nature of the facility
The Secretary argues that the use of the conjunctive “and” in §1910.331(c)(1) means
that, to qualify for the exemption set forth in §1910.331(c)(1), the facility must be used for every
activity set forth in §1910.331(c), i.e. the facility must be engaged in the control, transformation,
transmission, distribution and generation of electric energy. Because the Vault Room in Baldy
Hall did not generate electricity, the Secretary contends that the exemption does not apply. I am
not persuaded that the use of “and” was not meant to require that, to qualify for the exemption,
the facility must be engaged in each and every activity listed. That the exemption did not intend
to be an inclusive list is demonstrated by accompanying notes 1 and 3 to 1910.331(c):
Note 1: Work on or directly associated with installations of
utilization equipment used for purposes other than generating, transmitting, or
distributing electric energy (such as installations which are in office buildings,
warehouses, garages, machine shops, or recreational buildings, or other utilization
installations which are not an integral part of a generating installation, substation, or
control center) is covered under paragraph (a)(1) of this section.

   Note 3: Work on or directly associated with generation, transmission, or distribution
   installations includes:
     (1) Work performed directly on such installations, such as repairing
     overhead or underground distribution lines or repairing a feed-water
     pump for the boiler in a generating plant.
     (2) Work directly associated with such installations, such as line-
     clearance tree trimming and replacing utility poles.
     (3) Work on electric utilization circuits in a generating plant
     provided that:

                                             11

(A) Such circuits are commingled with installations of power
generation equipment or circuits, and
(B) The generation equipment or circuits present greater electrical
hazards than those posed by the utilization equipment or circuits (such
as exposure to higher voltages or lack of overcurrent protection).
(Emphasis added)

      In “Notes” 1 and 3, the SOL uses “or” when describing the types of activities the

facilities much engage in. Particularly instructive is Note 3, which explicitly states that line-
clearance tree trimming and replacing of utility poles can qualify for the exemption. Obviously,
such lines, while involved with the transmission and distribution of electricity, have nothing to
do with its generation.
I also find no merit in the Secretary‟s assertion that the Vault Room was only an area in
the basement of Baldy Hall, which was essentially filled with classrooms and, therefore, did not
qualify as a “building” within the meaning of the exemption. Lawrence Poturalski, an engineer
in the SUNY Buffalo facilities department, testified that the equipment located in the Vault
Room was designed for the transformation, transmission, or distribution of electrical power (Tr.
451). While Baldy Hall is clearly a building, the issue is whether the “building” must be used
exclusively for the listed purposes, or whether it can be, as here, a shared-use facility.
The exemption which states that the listed activities must be “located in buildings used
for such purposes…” can be read both ways. However, the scope provision at §1910.331(a) is
instructive:
(a) Covered work by both qualified and unqualified persons. The provisions of
§§1910.331 through 1910.335 cover electrical safety-related work practices for
both qualified persons (those who have training in avoiding the electrical hazards
of working on or near exposed energized parts) and unqualified persons (those
with little or no such training) working on, near, or with the following
installations:
(1) Premises wiring. Installations of electric conductors and equipment within
or on buildings or other structures, and on other premises such as yards, carnivals,
parking, and other lots, and industrial substations…

      Moreover, that the scope provision makes §§1910.331 through 1910.335 applicable to

installations of electric conductors and equipment “within or on buildings or other structures”
clearly implies that these buildings may have multiple uses beyond the generation, transmission
or distribution of electricity. I find no reason why the term “building” used in the scope provision
and the exemption should not be read in parallel. Thus, if the provisions of §§1910.331 through

                                              12

1910.335 can apply to the basement at Baldy Hall because it is a qualified “building,” then it is
also a building subject to the exemption, when work is performed by qualified persons.
Indeed, the Secretary has not articulated any reason why the building must be
exclusively for electrical functions, or any reason why the purposes of the standard would be
compromised if the exemption encompassed buildings used for multiple functions. Moreover,
the Secretary has issued a Letter of Interpretation that suggests that multiple use buildings can
qualify for the exemption.
That letter was not introduced into evidence, but may be found at:
http://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=INTERPRETATIONS&p_
id=22236 However, I take official notice of this public document. See Administrative
Procedure Act, 5 U.S.C. §556(e).The letter involves an inquiry where a facility was used both for
distribution activities (covered under §§1910.331 through 1910.335) and utilization activities
(which are not covered under §§1910.331 through 1910.335). The employer sought guidance
regarding whether the facility was covered under §§1910.331 through 1910.335 or other parts of
the electrical standards (specifically 29 C.F.R. §1910.269). The Secretary replied that:

            OSHA is concerned that using different work practices in these examples
   could lead to confusion for employees working on them. This confusion could
   result in serious accidents. In situations such as these, an employer would be
   expected to determine that these closely related installations are all either
   utilization or distribution and then require employees working on them to meet
   the work practice requirements of Subpart S or §1910.269, respectively, so as to
   have consistent work practices. Employers who do not adopt consistent work
   practices for working on the two “different” buses face the possibility of being
   cited for violation(s) of §1910.269, 1910 Subpart S or the general duty clause of
   the OSH Act if the inconsistencies pose hazards to employees.

   Notably, nothing in the letter suggests that the facility should be disqualified from being

covered under §§1910.331 through 1910.335 on the grounds that it was not being used
exclusively for the relevant electrical activities or implied that the facility could not be exempt
from §§1910.331 through 1910.335 because it was a multi-use facility. Rather, the Secretary
clearly stated that the employer needed to select compliance with either §§1910.331 through
1910.335 or §1910.269 simply to maintain consistency in the work practices.
Therefore, I find that the Vault Room was located in a building within the meaning of the
exemption set forth at §1910.331(c)(1).

                                             13

C. Nature of the Work
The Secretary asserts that Vault Room crew was engaged only in preventative
maintenance and repairs. Therefore, she asserts, the employees were not engaged in work “on or
directly associated with generation, transmission, or distribution installations.” According to the
Secretary, the type of activities covered by the exemption would be (1) work performed directly
on such installations, such as repairing overhead or underground distribution lines or repairing a
feed water pump for the boiler in a generating plant; (2) work directly associated with such
installations, such as line clearance-tree trimming and replacing utility poles; and (3) work on
electric utilization circuits in a generating plant. 29 C.F.R. §1910.331(c)(1), n. 3
I am not persuaded. What the Secretary considers simple maintenance work must be
viewed in the context of the totality of the work which took place in Baldy Hall. This was more
than a mere maintenance project. Major pieces of equipment were being replaced in the adjacent
room. As part of this project, SUNY found it advisable to do substantial maintenance and
adjustment to the switching gear in the Vault Room. The cleaning and testing of the Vault Room
equipment was an integral part of the major replacements in the Adjacent Room. As such, the
work in the Vault Room went well beyond a routine maintenance project, such as would be the
case with work associated with a regularly scheduled maintenance program. If clipping trees
around a power line falls within the exemption as “work directly associated” with electrical
installations, certainly the work taking place in the Vault Room at Baldy Hall would be similarly
qualified. I also note that O‟Connell chose a crew that who were all certified at the journeyman
or master electrician level; hardly the type of crew one would expect to be assembled for work
that was merely routine maintenance.
Accordingly, I conclude that the exemption set forth at §1910.331(c)(1) applied to work
being done by the qualified crew in the Vault Room of Baldy Hall and, therefore, that the
standards set forth at §§1910.331 through 1910.335 do not apply.
I note, however, that for each of the items that alleged a violation of a standard in
§§1910.331 through 1910.335, the Secretary, in her Amended Complaint, alleged violations of
alternative standards. Therefore, the status of those items will be resolved by determining
whether the Secretary established violations of those alternative standards.

                                             14

II. Personal Protective Equipment (PPE)
Facts
At the beginning of the shift, Foreman Schoenthal instructed his employees to wear
“appropriate” PPE (Tr. 58, 60). It was Schoenthal‟s opinion that the employees were well trained
and experienced and, therefore, would know what type of PPE was appropriate for the job (Tr.
60). Woodfield testified that he retrieved his PPE from his car, that the suit he wore was the only
one available and that he couldn‟t recall its rating (Tr. 212-213). Moreover, he testified that he
was the only employee who brought a protective suit into the Vault Room (Tr. 212).
The Compliance Officer (“CO”) testified that the gloves worn by Woodfield were rated
for 20KV (Tr. 46). He also testified that the Woodfield should have worn leather protectors over
his gloves (Tr. 65). The CO testified that he never asked and was not told by Woodfield that he
was wearing leather protectors (Tr. 115). However, Woodfield testified that his gloves were
equipped with the leather covering (Tr. 239, 254). NFPA 70E states that leather protectors worn
over insulating rubber gloves provide sufficient protection against arc-flash (Ex. RX-35).
When he tested and grounded the equipment in the Vault Room, Woodfield wore, a face
shield rated at 12 calories/cm2 attached to his hardhat (Tr. 44, Exs. P-38, pg. 5-6; P-39, p.27).
This was considered Class 2 protection (Tr. 130, 177).
Respondent introduced the testimony of its expert, Douglas Strang, an electrical engineer
with a Master‟s Degree in Industrial Engineering (Tr. 382). Strang testified that, using the “Lee
Equation” to calculate the effect of an arc-flash, Woodfield was outside the range of potential
injury (Tr. 419). The Secretary attempted to rebut Strang‟s testimony by calling its expert,
William DeWitt, who has a Master‟s Degree in Electrical Engineering. DeWitt would not accept
the accuracy of the “Lee Equation” when calculating the range of an arc-flash in a confined
space, such as a switch cabinet. DeWitt testified that one of the recognized weaknesses of the
“Lee Equation” is its failure to calculate the magnifying effect of an arc-flash blast in a confined
space. Rather, it is only accurate to calculate the force of an open air arc-flash. For confined
spaces, DeWitt uses a different formula which is termed “arc-in-a-box.” However, the arc-in-a-
box effect has not been tested for voltages above 15 KV (Tr. 460-463). DeWitt explained that
because the arc-in-a-box effect has not been tested for voltages above 15K, the computer
equations automatically revert to the Lee equation above that voltage (Tr. 463). Although
DeWitt attempted to rebut the accuracy of the “Lee Equation” when calculating the effects of an

                                             15

arc-flash in a confined environment, he did not offer his own calculations.
Item 2
Item 2 alleges that O‟Connell violated 29 CFR §1910.132(d)(1)(ii) on the grounds that,
an employee in the Vault Room, entered the transformers and load switches, tested for the
absence of voltage and applied protective grounds, but was “not informed about the types of PPE
that he needed to wear to protect him from the electrical hazards present or likely to be present in
this workplace where the potential voltage in the above mentioned equipment was 34,500 volts-
ac.”
The cited standard states:
1910.132 General requirements.
* * *
(d) Hazard assessment and equipment selection. (1) The employer shall
assess the workplace to determine if hazards are present, or are likely to be
present, which necessitate the use of personal protective equipment (PPE). If
such hazards are present, or likely to be present, the employer shall:
* * *
(ii) Communicate selection decisions to each affected employee

   The Secretary also alleged, in the alternative, a serious violation of 29 CFR

§1910.269(a)(2)(ii)(D) on the grounds that employees were not trained and familiar with the
proper use of protective gear. That standard provides:
1910.269 Electric power generation, transmission, and distribution.
(a) General
* * *
(2) Training.
* * *
(ii) Qualified employees shall also be trained and competent in:
* * *
(D) The proper use of special precautionary techniques, personal
protective equipment, insulating and shielding materials, and insulated tools for
working on or near exposed energized parts of electric equipment.

   The Secretary proposed a penalty of $6300 for this violation.


                                  Arguments
   Secretary
   According to the Secretary, it is undisputed that Foreman Schoenthal only instructed his

employees to wear “appropriate” PPE. In response, Woodfield wore Class 2 PPE, when the

                                            16

conditions called for him to wear Class 4. The Secretary also asserts that Woodfield was not
competent to choose the appropriate PPE. Rather than select the proper PPE, he simply put on
what he had available in his car. He never made an attempt to ascertain whether the PPE in his
possession was adequate protection in the event of an arc-flash. That other members of the Vault
Room crew did not even bring PPE into the room shows a lack of adequate training and
underscores O‟Connell‟s responsibility to select the appropriate PPE. The Secretary also points
out that the Commission has said that “employers cannot count on employees‟ common sense,
experience, training by former employers or a union to preclude the need for specific
instruction.” Par Electrical Contractors, Inc., 20 BNA OSHC 1624 (No. 99-1520, 2004))
Respondent
O‟Connell points out that Foreman Schoenthal communicated the need to wear
appropriate PPE, and before the job began, explained the nature of work. Woodfield was trained
and competent in the proper use of PPE. He had 20 years of experience as an electrician and has
been a master electrician since 1993. He also had classroom training and training in arc-flash
hazards.
The Secretary‟s position that an employer cannot rely on an experienced electrician to
select the appropriate PPE as a job unfolds has been squarely rejected. Capital Electric Line
Builders of Kansas, Inc. v. Marshall, 678 F.2d 128, 131 (10th Cir. 1982). Also in El Paso Crane
& Rigging, 16 BNA OSHC 1419 (1993) the Commission held that an employer‟s instructions are
not necessarily deficient because they allow employees discretion as to how to proceed,
particularly when circumstances are such that no one form of protection is capable of being used
every time. Here, the Secretary failed to show that Schoenthal‟s instructions were insufficient.
Turing to the alternative standard, O‟Connell argues that Woodfield, who did the initial
testing and grounding of equipment, made his PPE selection decisions upon the particular tasks
he performed as work progressed. Woodfield was plainly qualified to make such PPE selections.
Discussion
The duty imposed by 29 CFR §1910.132(d)(1)(ii) is clear. The employer has the explicit
obligation to (i) assess the workplace for hazards necessitating the use of PPE; and (ii)
communicate its selection decision to each employee. Here, the employer did not communicate a
selection decision. Rather, realizing that PPE was required, the foreman simply told the
employees to wear “appropriate” PPE, thus leaving the selection decision to the employees.

                                            17

The cases relied on by respondent are clearly distinguishable. In Capital Electric Line
Builders, an employee working on a utility line was electrocuted while removing a ground clamp
when one hand came into contact with an energized switch. As a result, the employer was cited
for violating (1) 29 C.F.R. § 1926.950(c)(1) for allowing an employee to work too closely to
energized parts without insulating equipment; (2) 29 C.F.R. §1926.954(e)(2) for allowing an
employee to remove grounds without using insulating tools; and (3) 29 C.F.R.
§1926.556(b)(2)(v) for allowing an employee to work in an aerial bucket without a restraining
belt. The evidence demonstrated that while the employee took insulated gloves into his bucket,
he was not wearing them at the time of the violation. Finding that the employer established the
Unpreventable Employee Misconduct (“UEM”) defense, the 10th circuit noted that it was
undisputed that the employer provided its employees with all required safety equipment, held
regular meetings, disseminated information, and enforced its work rules. The court also noted
that the employee was a highly trained and experienced journeyman lineman. The court found
that the standards governing work in energized areas “inherently require a judgment call by the
employee as to when „cover-up‟ is necessary.” 678 F.2d at 131.Contrary to O‟Connell‟s assertion,
Capital Line Builders does not state that an employer can rely on an experienced electrician to
select appropriate PPE. Rather, it goes to an employer‟s right to rely on an experienced employee
to know when to use that equipment. Indeed, the standards cited in Capital Line Builders require
the employer to provide protective equipment. In that case, the appropriate PPE was provided,
but not used.
In El Paso, an employee was killed after falling from a building under construction.
Safety nets were not provided. As a result, the employer was cited for, inter alia, a violation of
§1926.21(b)(2) for failing to instruct each employee on how to recognize and avoid possible
exposure to fall hazards. The Commission noted that the standard‟s command to “instruct each
employee in the recognition and avoidance of unsafe conditions” is so general and subjective that
the Commission and the courts have seen fit to read into it a reasonableness standard. That is, to
establish noncompliance, the Secretary must establish that the cited employer failed to provide
instructions that a reasonably prudent employer would have given in the same circumstances.
The Commission found that the Secretary failed to prove that the instructions given were
significantly less than a reasonably prudent employer would have given in the same
circumstances. It stated that the sufficiency of a company‟s safety instructions “must be judged in

                                             18

the context of the safety program‟s substance.” 16 BNA OSHC at 1426. The Commission
concluded that an “employer‟s instructions are not necessarily deficient because they allow the
employees discretion as to how to proceed, particularly where the working circumstances are
such that no one form of protection is capable of being used every time.” Id.
The objective obligation imposed by §1910.132(d) differentiates it from such standards
as §1926.21(b)(2) which is an “instruction” standard and therefore by its nature subjective. Here,
however, the employer has an objective duty to assess the hazards and communicate his selection
to each affected employee. The employer does not satisfy his duty under §1910.132(d) by
delegating his responsibility to make the assessment to the employee, no matter how trained,
competent or qualified he may be. That may go to the gravity of the hazard, but not to whether
the standard was violated. Here, by only instructing its employees to wear “appropriate” PPE, K
knowing that PPE was required, Schoenthal violated the express mandate of the standard to
select the PPE its employees should have worn. Accordingly, the item 2, alleging a violation of
29 C.F.R. §1910.132(d)(1)(ii) is affirmed.
Having found a violation of 29 C.F.R. §1910.132(d)(1)(ii), it is unnecessary to address
the alternatively cited standard.
Item 5
Item 5 alleges a serious violation of 29 CFR §1910.138(a) on the grounds that O‟Connell
failed to select and require its employees to use appropriate hand protection for exposure to
thermal burn and other harmful substances.
The cited standard provides:
1910.138 Hand protection.
(a) General requirements. Employers shall select and require employees
to use appropriate hand protection when employees‟ hands are exposed to hazards
such as those from skin absorption of harmful substances; severe cuts or
lacerations; severe abrasions; punctures; chemical burns; thermal burns; and
harmful temperature extremes.

   The Secretary proposed a penalty of $6300 for this violation.
                                   Arguments
   Secretary
   The Secretary points out that Schoenthal only instructed employees to use appropriate

PPE. He did not specifically select what gloves they should wear. It was established that

                                            19

Woodfield tested switches and grounded transformers in vault room. Woodfield should have
considered them energized at 34.5 KV until tested and grounded, and he should have worn
gloves to protect himself at that level. Instead he wore only gloves that protected him to 20 KV.
Safety Manager Sandvik and Expert witness Strang confirmed that he should have worn category
4 gloves, instead of the category 2 gloves he was wearing
The Secretary also argues that O‟Connell belatedly raised at trial the assertion that
Woodfield used leather covers on his gloves and that Woodfield never informed the CO that he
used the leather covers. In any event, Woodfield confirmed that leather covers only designed to
protect his 20 KV gloves from damage and did not provide any additional protection from
electrical hazards.
Respondent
O‟Connell asserts that the gloves were adequate. It points out that the standard at 29
C.F.R. §1910.296(l)(2) sets minimum approach distances for which employees need to wear
insulated gloves to protect against shock hazard. That standard, at Table R-6, indicates that at 35
KV, phase-to-phase, minimum distance is 2 feet 7 inches. Therefore, gloves only need to be worn
when working inside that distance. However, the Secretary never demonstrated that Woodfield‟s
hands passed inside that minimum approach distance. Rather, the evidence shows that he
performed the testing and grounding using a voltage detector attached to the end of a six-foot
long hot stick to test for the absence of voltage. Therefore, no gloves were required and the
gloves he wore were sufficient to protect against shock hazards.
Moreover, respondent argues that the 34.5 KV volts is a phase-to-phase measurement.
Woodfield testified that 34.5 KV phase to phase is equivalent to 19 KV volts ground-to-ground.
Accordingly, the gloves which were rated for 20 KV were sufficient. Also, per standard practice,
Woodfield wore leather coverings over his gloves. The CO, who assumed that Woodfield did not
wear leather protectors, testified that he should have worn them. However, the CO never asked
Woodfield if he was wearing the leather protectors. According to NFPA 70E, leather protectors
worn over insulating gloves provide sufficient hand protection against arc flash (RX 35 at 6).
This is not disputed by the Secretary.
In any event there was no hazard within the purview of 29 C.F.R. §1910.138(a).
Electrical shock and arc-flash hazards are not among the hazards within the scope of 29 C.F.R.
§1910.138(a) which is limited to mechanical and chemical hazards “such as those from skin

                                            20

absorption of harmful substances, severe cuts or lacerations, severe abrasions, punctures,
chemical burns, thermal burns, and harmful temperature extremes.” PPE to protect against
electrical shock hazards come within 29 C.F.R. §§1910.269(l)(2) or 1910.335(a)(1)(i). Therefore,
the cited standard does not even apply to any hazard to which Woodfield was exposed.
Finally, O‟Connell argues that items 2, 5 and 8 all relate to PPE and overlap. Therefore if
any of these items are affirmed, they should be grouped for penalty purposes.
Discussion
The first issue to address is whether the cited standard applies to the hazards to which
Woodfield was exposed. The problem with O‟Connell‟s argument is that it mixes the concept of
the “insulating” (electrical) value of gloves with its “thermal” value. The citation specifically
addresses “thermal hazards.” The standard requires protection against “thermal burns; and
harmful temperature extremes.” Here, one of the hazards is arcing which presents thermal
hazards. It is noteworthy that the Secretary is not claiming that the gloves were not insulated,
which would implicate an electrical hazard.
The Commission has recognized the difference between thermal hazards and electrical
hazards. In North Landing Line Constr. Co., 19 BNA OSHC 1465 (No. 96-721, 2001), the
Commission noted that the arc-over between the phases creates a fireball that engulfs employees
and causes thermal burns. There was also general testimony that, in addition, electric current can
flow through the employee, causing electrical burns. I would also note that, in the ALJ decision
in North Landing Line, Judge Rooney clearly explained that electrical burns are caused by
current passing through the body, and that thermal burns are caused by external heat such as that
produced in an arc blast.
Protecting against electrical hazards means that the PPE has to have insulation value
against an electrical current. Protection against thermal energy refers to protection against heat.
Here, the quality of the PPE being discussed, though based on current, is measured in calories,
which is a measure of heat. Clearly, the higher the voltage, the greater the heat that will be
generated at any given distance. Thus, to adequately guard against heat, PPE for 35.5 KV will
require a higher caloric protective value than PPE needed to guard against 20 KV. Also, leather is
not an electrical insulator. However, it does provide thermal protection. O‟Connell implicitly
recognizes this by arguing that the gloves had leather covers.
Respondent argues that there was no hazard because Woodfield maintained the minimum

                                             21

distance set forth in Table R-6. These minimum distances do not apply to thermal hazards, since
the purpose of maintaining a minimum distance is to prevent an employee from bringing a
conductive object, such as his hand close enough to the source of the current to cause an arcing.
Rather, this relates to the insulating value of the gloves, which is not at issue here. When wearing
PPE for protection against heat, one assumes that an arcing can occur no matter what the
distance the employee‟s hand may be from the source of the electricity.
During work, it is possible that some event other than an employee coming within the
minimum distance could cause an arcing. (In North Landing Line Constr. Co, the Commission
discusses expert testimony that describes possible causes of an arcing besides employees coming
within the minimum distance). Certainly, the farther from the source, the lower the temperature
from arcing, but that has nothing to do with being too far to cause an arcing. So viewed, the
relevant measure is the heat generated from the arcing at the distance the employee is from the
arc, not if he would come within the minimum distance that could set off an arcing. Finally, I
would note that both 29 C.F.R §§1910.269(l)(2) or 1910.335(a)(1)(i), which respondent asserts
applies, refer to electrical hazards, not thermal hazards. The citation specifically addresses
“thermal” hazards. Accordingly, I find that the cited standard applies.
Having found that the standard applies, the next issue is whether the gloves were
appropriate for the thermal hazard presented. The evidence is that gloves were rated at 20 KV.
Respondent argues that the 34.5KV is based on phase-to-phase which is equal to 19 KV phase-
to- ground (Tr. 253-255). However, it is unclear whether the rated voltage is phase-phase or
ground-ground. This was brought up by Woodfield, who testified that he was wearing gloves
that were rated at 20 KV to ground (Tr. 238), but was not supported with any other testimony or
evidence and, therefore, remains uncorroborated.
While the distinction between phase-to-phase and phase-to-ground seems troubling,
respondent‟s Corporate Safety Manager, William Sandvik, testified that Woodfield was wearing
Category 2 PPE but should have been wearing Category 4 (Tr. 177). Foreman Schoenthal
testified that whether they should have been wearing Category 2 or 4 depended on the task they
were performing (Tr. 320). He then testified that Woodfield should have been wearing Category

  1. The credibility of his testimony was undermined when he was asked to read his own
    deposition where he stated that they should have been wearing Category 4 (Tr. 321-322).
    Woodfield testified that his gloves were rated at 20 KV to ground (Tr. 238). The CO testified that

                                             22
    

    Woodfield was wearing gloves rated at 20 KV, but that when actually working on the switchgear
    inside the cabinet, his gloves should have been rated at 35 KV (Tr. 64-65). This was substantially
    supported by respondent‟s expert witness, Strang. In his report, Strang stated that while working
    with a hot stick, and maintaining a six foot distance from the switchgear, gloves rated for 35 KV
    were not required (Ex. RX-35, p. 4-6). This was consistent with his overall view that, at that
    distance, Woodfield‟s PPE was sufficient (Tr. 419, Ex. RX-35, p.7). However, at the hearing,
    Strang testified that, when opening the inner door to the cabinet where he would be closer to the
    switchgear, he should have been wearing a 44 calorie suit, but he was only wearing an 8 calorie
    suit (Tr. 428-429). Accordingly, I find that the preponderance of the evidence establishes that
    Woodfield should have been wearing gloves rated for 35 KV.
    Regarding the leather covering over the gloves, the Secretary complains that the CO was
    not told about them until later (Tr. 131). However, there is no evidence that he specifically asked
    about them (Tr. 115). This is a credible explanation, since the evidence demonstrates that leather
    coverings are customarily worn to protect the rubber gloves (Tr. 238). Therefore, there would be
    no reason for Woodfield to volunteer this information. Nonetheless, I do not find that the gloves
    increased the protective factors inherent in the gloves worn by Woodfield. As Woodfield
    testified, the glove comes in two pieces: a rubber piece designed to protect the worker from
    electricity and a leather cover designed to protect the glove from damage (Tr. 238). As a two-
    piece glove, I find that the rating includes use of the leather protector.
    Respondent also argues that NFPA 70E at 130.7(C)(13) provides that “[w]here insulating
    rubber gloves are used for shock protection, leather protectors shall be worn over the rubber
    gloves” (RX-35, p.6). The flaw in respondent‟s argument is that the NFPA specifically refers to
    the use of leather coverings “[w]here insulating rubber gloves are used for shock protection.”
    Here, however, the issue is whether they provided sufficient thermal protection.
    I would also note that the standard clearly requires the employer to “select and require
    employees to use appropriate hand protection.” As with item 2, supra, the evidence demonstrates
    that the choice of PPE was left to the individual employee. The failure of Schoenfeld to select the
    appropriate gloves for Woodfield further establishes that O‟Connell violated the standard.
    Accordingly, I find that the standard applies and that the Secretary has established, by a
    preponderance of the evidence, that the gloves worn by Woodfield were inadequate for the
    thermal hazards to which he was exposed. The item is, therefore, Affirmed.

                                              23
    

    Item 8
    Item 8 alleges a serious violation of 29 C.F.R. §1910.335(a)(1) on the grounds that
    O‟Connell failed to ensure that employees who were exposed to eye and face injuries from
    electrical arc flashes or from flying objects resulting from electrical explosions wore adequate
    PPE.
    The standard provides:
    Sec. 1910.335 Safeguards for personnel protection.

      (a) Use of protective equipment--(1) Personal protective equipment.
     (i) Employees working in areas where there are potential electrical
     hazards shall be provided with, and shall use, electrical protective
     equipment that is appropriate for the specific parts of the body to be
     protected and for the work to be performed.
    
     Note: Personal protective equipment requirements are contained in
     subpart I of this part.
    
     (ii) Protective equipment shall be maintained in a safe, reliable
     condition and shall be periodically inspected or tested, as required by
     Sec. 1910.137.
      (iii) If the insulating capability of protective equipment may be
     subject to damage during use, the insulating material shall be protected. (For example,
     an outer covering of leather is sometimes used for the protection of rubber insulating
     material.)
     (iv) Employees shall wear nonconductive head protection wherever
     there is a danger of head injury from electric shock or burns due to
     contact with exposed energized parts.
     (v) Employees shall wear protective equipment for the eyes or face
     wherever there is danger of injury to the eyes or face from electric
     arcs or flashes or from flying objects resulting from electrical
     explosion.
    

    As noted, supra, I have found that this standard was inapplicable to the Vault Room
    pursuant to the exemption in 29 C.F.R. §1910.331(c). However, the Secretary alleges in the
    alternative, a violation of 29 C.F.R. §1910.133(a)(1) which states:
    Sec. 1910.133 Eye and face protection.

     (a) General requirements. (1) The employer shall ensure that each
     affected employee uses appropriate eye or face protection when exposed
     to eye or face hazards from flying particles, molten metal, liquid
    
                                            24
    

    chemicals, acids or caustic liquids, chemical gases or vapors, or
    potentially injurious light radiation.

                                    Arguments
      Respondent:
      Respondent argues that electric shock and arc-flash hazards are not among the hazards
    

    within the scope of §1910.133. Section 1910.133 is limited to mechanical and chemical hazards
    and “injurious light radiation.” Thus, the regulation does not even apply to the hazards cited.
    Respondent next contends that, even if the standard applies, the eye and face protection
    worn by Woodfield provided adequate protection against the hazards present. As discussed,
    supra, Woodfield was well outside the 2‟7” approach distance so he was not exposed to a shock
    hazard. Strang calculated an approach distance of 6 feet would have incident energy of 11
    cal/cm2. Thus, at any distance equal or greater than 6 feet, Woodfield‟s face shield, which was
    rated for over 12 cal/cm2, would have provided a greater level of protection than the incident
    energy.
    The Secretary‟s rebuttal witness, DeWitt, criticized Strang for not accounting for the arc-
    in-a-box effect. However, DeWitt‟s own preferred method does not apply to systems operating at
    34.5 KV (Tr. 452). Thus, DeWitt did not provide an alternative estimate and never specifically
    said that he believed the incident energy would have been higher than Strang calculated.
    Therefore, the only evidence in the record establishes that the incident energy to be protected
    against at 6 feet would have been 11 cal/cm2 and Woodfield‟s face shield provided proper
    protection against the hazards a reasonable employer could expect him to encounter.
    Secretary
    The Secretary argues that Woodfield wore a face shield that was rated at 12 calories and
    provided inadequate protection against 34.5 KV arc flash. According to the Secretary, it is
    undisputed that there was a reasonable probability of injury from a vault room arc-flash. That is
    why Schoenthal conducted a safety meeting, locked and tagged out equipment, and instructed his
    crew to test for the presence of voltage and apply personal grounds. A “reasonable” employer,
    familiar with the conditions would have recognized the hazard. Indeed, although Schoenthal
    recognized the hazard, he failed to specify the type of eye and face protection the crew should
    have worn. Moreover, in its safety manual, O‟Connell cautions employees that arc hoods should
    be worn when exposed to potential higher energy levels.

                                              25
    

    The Secretary notes that respondent‟s expert, Strang, conducted an arc-flash simulation
    and concluded that Woodfield wore adequate PPE when standing 6.5 to 7.5 feet away. However,
    the Secretary argues that her rebuttal expert, DeWitt, discredited the simulation on grounds that it
    applied only to an open air arc-flash. Here, we were dealing with an arc-flash occurring in a
    confined space, or an “arc in a box.” The Secretary argues other flaws in Strang‟s testimony. For
    example, Strang conceded that his simulation was based on figures obtained by a third party.
    That third party was the National Grid in 2008. However, Strang did not verify that the numbers
    on which his results were based were still applicable on May 16, 2009 (SOL at 38).

                                  Discussion
     I find that the Secretary has failed to establish a violation of §1910.133. Under that
    

    standard, the Secretary must show that the vault room presented hazards associated with flying
    particles, glare and injurious light radiation. However, there was no evidence to establish that
    employees were exposed to flying particles or glare, or even if they were exposed, that the face
    shields they wore were inadequate to protect them from those hazards. Indeed, there is nothing in
    the record addressing those hazards. Rather, the entire thrust of the Secretary‟s efforts were to
    establish that the eye and face protection worn was inadequate to protect employees from the
    heat generated from an arc-flash at 35.5 KV. That is not the hazard addressed by the standard.
    As to the injurious “light radiation,” a review of the standards makes it clear that the
    cited standard addresses light in its simplest form, not in the physics context where electrical
    energy is a form of light. For example, at §1910.133(a)(5), the standard discusses protection
    from light radiation in the context of welding, where the light is intense and could burn the eyes.
    There is no evidence that the face shield worn by Woodfield did not have protection against light
    radiation. Also, the record does not indicate whether any of the face shields targeted by the
    Secretary included tinted visors designed to reduce the effect of light from an arc-flash.
    Moreover, when an employee is welding, the light is constant, focused and requires heavily
    tinted eye protection. Here, heavily tinted eye protection as a precaution against a possible arc-
    flash would likely make it difficult, if not impossible for the employee to see his work or
    navigate safely around the Vault Room.
    Given this finding, it is not necessary to determine the weight to be given to the
    testimony of the two experts on this matter.

                                             26
    

    Accordingly, this item is vacated.
    Penalty
    The Secretary classified both items 2 and 5 as serious and proposed a penalty of $6300
    for each item. A violation is serious where the evidence demonstrates that the likely result of a
    failure to comply with the standard is death or serious physical harm. Beverly Enterprises, Inc.,
    19 BNA OSHC 1161, 1188 (No. 91-3144, 2000)(Consolidated).
    Regarding item 2, the evidence establishes that having been instructed on the nature of
    the PPE that was required, respondent‟s employees, made their own decisions regarding what
    PPE they would wear. This resulted in Woodfield retrieving whatever PPE he had in his car
    which, as demonstrated supra, was inappropriate for the tasks he was undertaking. This could
    have resulted in serious harm from electrical burns (Tr. 59-60). As to item 5, the evidence
    demonstrates that, in the event of an arc-flash or other electrical accident, the failure of
    employees to wear appropriate protective gloves could result in serious burns to an employee‟s
    hands. (Tr. 61) Accordingly, I find that both items were properly characterized as serious.
    Section 17(j) of the Act, 29 U.S.C. § 666(j), requires that, in assessing penalties, the
    Commission must give "due consideration" to four criteria: the size of the employer's business,
    the gravity of the violation, the employer's good faith, and its prior history of violations. S & G
    Packaging Co., 19 BNA OSHC 1503, 1509 (No. 98-1107, 2001). The CO testified that the
    violation was considered to be of high gravity and severity with a “greater” probability of an
    incident. Based on these factors, the Secretary assigned a base penalty of $7000. The Secretary
    deducted 10% for O‟Connell‟s history, which included no serious or repeat violations in the past
    three years. No credit was given for either size or good-faith (Tr. 60-62, Ex. P-2). These factors
    were applied to all of the alleged violations (Tr. 62). I find that the Secretary properly considered
    the section 17(j) factors when proposing the penalty and that a penalty of $6300 is appropriate
    for each of the items. .
    Respondent argues that the items are sufficiently similar that the penalties should be
    combined. The Commission has the discretion to combine penalties where a single action will
    abate both violations. H.H. Hall Constr. Co., 10 BNA OSHC 1042, 1046 (No. 76-4765, 1981).
    Here, Schoenthal testified, at different times that Woodfield should have worn either Category 2
    or 4 gloves. This strongly suggests that he was confused regarding the appropriate Category of
    gloves that would have been appropriate for the worksite. Therefore, even if Schoenthal had

                                              27
    

    designated the gloves that Woodfield should have worn, there was no guarantee that his selection
    would have been appropriate. Accordingly, I decline to combine the items for penalty purposes.

III. Work Practices/Signs
A. Facts
When the Vault Room crew completed their work on switch S3, they removed the
grounds and closed the cabinet (Ex. P-28). At 1:10 pm, the crew completed work on switch
cabinet S2. Again, the crew removed the grounds and closed that door (Tr. 361-362, Ex. P-28).
Switch cabinets S1 and S4 had the cabinet door and inside screen door shut throughout the
operation (Tr. 354-356, RX-24). However, the doors to all four switch cabinets could be opened
with a single Yale Key (Tr. 358).
The evidence demonstrates that the 25B switches (S1 and S4) which remained energized,
had a hasp with a lock and tag which was installed by Schoenthal. The tag had his name and
phone number on it and was not supposed to be removed without contacting him. (Tr. 355)
Similar tags on the 53A switches (S2 and S4), were removed to allow the Vault Room crew to do
their work. (Tr. 356, 360) Also, above the 25B switch was a small red and white sticker that
warned that there was high voltage (Tr. 356, Exhibit RX-24). Despite this evidence, at
Stipulation #31 of its opening brief, respondent states that “O‟Connell Electric did not install any
special tags to remind its employees that two electrical switches remained energized.”
Besides the basic warning signs that applied to all four of the switches, respondent did
not erect any barricades or post attendants to prevent unimpeded access to the two energized
switches. (Tr. 63, Ex. P-23, p 18, Ex. P-24, p. 8, Ex. P-25, p.5, Ex. P-26, p.7)

                                          Item 4b

   Item 4(b) originally alleged a violation of 29 C.F.R. §1910.333(a)(2) on the grounds that

O‟Connell failed to institute any “other” safety related work practices to protect employees in the
Vault Room from contacting switches S1 and S4, which remained energized. The Secretary
specifically noted that respondent did not erect any barricades or post attendants to prevent
unimpeded access to the two energized switches or post any signs specifically warning
employees that switches S1 and S4 remained energized.
The cited standard states:

                                             28

§1910.333 Selection and use of work practices.
(a) General
* * *
(2) Energized parts. If the exposed live parts are not deenergized
(i.e., for reasons of increased or additional hazards or infeasibility),
other safety-related work practices shall be used to protect employees
who may be exposed to the electrical hazards involved. Such work
practices shall protect employees against contact with energized circuit
parts directly with any part of their body or indirectly through some
other conductive object. The work practices that are used shall be
suitable for the conditions under which the work is to be performed and
for the voltage level of the exposed electric conductors or circuit
parts. Specific work practice requirements are detailed in paragraph (c)
of this section.

     However, as noted, supra, pursuant to §1910.331(c), the standards at §§1910.331

through 1910.335 are not applicable to the activities of the Vault Room crew.
In her amended complaint, however, the Secretary alleges, in the alternative, a violation
of §1910.269(l)(2) on the grounds that respondent failed to ensure that no employee in the Vault
Room approached or took any conductive object closer to exposed energized parts than set forth
in Tables R-6 through R-10. That standard provides:
1910.269 Electric power generation, transmission, and distribution.
* * *
(l) Working on or near exposed energized parts. This paragraph applies to work on
exposed live parts, or near enough to them, to expose the employee to any hazard they
present.
* * *
(2) Minimum approach distances. The employer shall ensure that no employee
approaches or takes any conductive object closer to exposed energized parts than set forth
in Table R-6 through Table R-10 [approximately 21/2 feet], unless: [omitted]

                                  Arguments
   Secretary

   The Secretary points out that foreman Schoenthal knew that the Yale Key opened the

doors to all the cabinets. Since the key was available to all the members of the Vault Room crew,
he should have taken additional precautions to ensure that no one could accidentally come into
contact with live switches S1 and S4. The Secretary specifically notes that respondent failed to
erect any sort of barricade or post attendants to prevent unimpeded access to the two energized

                                            29

switches. Respondent relied on pre-existing safety signs, but the signs are common on electrical
equipment and the ones at the site did nothing to distinguish the live switches from the de-
energized switches. The facts show that respondent did nothing to obstruct access to switches 1
and 4. The record is also devoid of evidence that O‟Connell installed any device that would have
prevented employees from coming within the Minimum Allowed Distance with the 34.5 KV
circuits.
Respondent

    O‟Connell points out that the burden is on the Secretary to make a prima facie showing

of knowledge. Schoenthal was never aware that [redacted] was opening the cabinet S4.
Woodfield was similarly unaware. He was working in front of the Transformer T1 and his view
of [redacted] was obstructed. Switches S1 and S4 were closed and locked. Employees were
instructed not to open or enter them. [redacted] was an experienced journeyman electrician and
was familiar with the hazards associated with working on medium-voltage systems. That
[redacted] possessed the Yale key that unlocked S4 is irrelevant. The energized parts were
enclosed within the cabinet and the Secretary cites no regulatory requirement that such an
enclosure must be locked, let alone that employees not gain access to the key to such a cabinet.
Therefore, O‟Connell contends that the Secretary failed to make a prima facie showing of
knowledge.
Moreover, even if prima facie knowledge were shown, [redacted] entry into switch S4
was the result of unpreventable employee misconduct. [redacted] was specifically instructed that
S4 was energized, not within scope of work and not to be entered. The Vault Room crew was
instructed to keep out of S4. O‟Connell has an established safety program that provides for
periodic safety training, on-site “tool box” safety talks and it regularly enforces it safety policies.

                                     Discussion

        As noted, supra, as part of her prima facie case the Secretary must demonstrate that the

employer knew, or with the exercise of reasonable diligence could have known of the existence
of the hazard. Atlantic Battery Co., 16 BNA OSHC at 2138. To meet her burden here, the
Secretary was required to demonstrate that O‟Connell knew, or with the exercise of reasonable
diligence could have known that a member of the Vault Room crew might come within the
Minimum Approach Distance set forth in Table R-6 of the cited standard. I find that this item

                                               30

must be vacated because the Secretary has failed to make out a prima facie showing of
knowledge.
The preponderance of the evidence establishes that the employees who worked in the
Vault Room were highly trained, experienced and competent electricians, all of whom attained,
at a minimum, journeyman status. The electrified components of the 25B switches (Switch
cabinets S1 and S4) were in locked cabinets. This prevented employee access to the energized
components therein, and prevented any crew member from coming within the Minimum
Approach Distance either by the necessities of the job or by accident. The evidence also
establishes that before the day‟s shift began, Foreman Schoenthal held a meeting where he
explained the job to the crew and instructed the crew that they were to work only on the two
center switch cabinets S2 and S3 and not to open either of the two end cabinets S1 and S4 (Tr.
278, 300, 303, 346-347, 349-350). I also note that Schoenthal testified that he placed a hasp with
a lock and tag on each of four (Tr. 355-356, 360). Those tags contained his name and phone
number, indicating that he was to be contacted before the switches were opened (Tr. 355-356, Ex.
P-25). The lock and tag on the 53A switches had been removed to allow the Vault Room crew to
do their work (Tr. 360). They remained on the 25B switches. Although the same key opened the
locks on all four cabinets, the point remains that [redacted] knew that the de-energized cabinets
S2 and S3 had the lock and tag removed, while the energized cabinets S1 and S4 remained
locked and off-limits to the crew, and contained Schoenthal‟s tags. Even after the work was
completed on S2 and S3 and their doors locked, there is no evidence that the tags were replaced.
There is no evidence to suggest why [redacted] opened switch cabinet S4. The Secretary
posits that it was accidental and caused by insufficient/inappropriate work practices by
O‟Connell. However, that is purely speculative. I find that the evidence fails to establish that
O‟Connell knew, or with the exercise of reasonable diligence, could have known, that an
employee would violate his instructions, open a locked and tagged cabinet that was not relevant
to his work, and bring a conductive object within the Minimum Approach Distance set forth in
Tables R-6 through R-10. Accordingly, the item is vacated.

                                          Item 13

   Item 13 alleges a serious violation of 29 CFR §1910.335(b)(1) on the grounds that

O‟Connell failed to install safety signs, safety symbols or accident prevention tags to warn

                                             31

employees of electrical hazards in switches S1 and S4.The standard provides:
1910.335 Safeguards for personal protection.
* * *
(b) Alerting techniques. The following alerting techniques shall be
used to warn and protect employees from hazards which could cause injury due to
electric shock, burns, or failure of electric equipment parts:
(1) Safety signs and tags. Safety signs, safety symbols, or accident
prevention tags shall be used where necessary to warn employees about
electrical hazards which may endanger them, as required by Sec.
1910.145.

     As noted, supra, I find that the cited standard does not apply to the work performed by

the Vault Room crew. However, in her amended complaint, the Secretary alternatively alleges a
violation of 29 C.F.R. §1910.145(f)(3) on the grounds that:

   tags were not used as a means to prevent accidental injury or illness to employees
   exposed to hazardous or potentially hazardous conditions, equipment or
   operations which were out of the ordinary, unexpected or not readily apparent.
   Tags were not used until the identified hazard was eliminated or the hazardous
   operation completed. Respondent did not employ any other positive means of
   protection.

   The standard states:

     Sec. 1910.145 Specifications for accident prevention signs and tags.
                *       *          *
     (f) Accident prevention tags
                *        *          *
     (3) Use. Tags shall be used as a means to prevent accidental injury
     or illness to employees who are exposed to hazardous or potentially
     hazardous conditions, equipment or operations which are out of the
     ordinary, unexpected or not readily apparent. Tags shall be used until
     such time as the identified hazard is eliminated or the hazardous
     operation is completed. Tags need not be used where signs, guarding or
     other positive means of protection are being used.

   Specifically, the Secretary asserts that there was a fixed „Yale Lock‟ on the outer
   door of each switch. A key had to be inserted into this lock in order for an
   employee to enter the switch to perform preventative maintenance. All four
   switches had their „switching handle‟ in the down position (open) and the
   foreman‟s lock and tag was attached to each handle. All of the switches looked
   almost identical, but inside two of the switches, there were exposed parts at
   34,500 volts. A single key entrusted to the foreman could open the door to any of
   the four switches, since the „Yale Locks‟ were all keyed the same. An employee

                                           32

entered switch [S4] with live parts and an arc flash occurred engulfing the
employee in flames causing severe burns. Accident prevention tags which could
have prevented this injury were not placed on switches [S1 and S4] to indicate
that they contained live parts and were unsafe to enter.

                                          Arguments
   Secretary

   The Secretary notes that it is undisputed that O‟Connell did not install any safety signs,

symbols or tags in vault room. Rather, it relied on switches cabinet enclosures and pre-existing
safety signs to guard against exposure to electrical hazards associated with switches S1 and S4.
All of cabinets looked alike and Yale Key granted access to them all. Also it is undisputed that
the “Danger High Voltage” signs that were in the Vault Room are common on electrical
worksites and equipment. Therefore, it was incumbent on respondent to take additional steps to
ensure that the energized and de-energized switches were distinguishable. It failed to do so.
Also, respondent admitted that when the Vault Room crew was finished with the required
maintenance and repairs for cabinet S3, they removed the grounds and closed the cabinet, thus
making them indistinguishable from the energized cabinets.
Respondent
Respondent points out that the evidence shows that guarding was in place to isolate
employees from the energized parts within S4. These energized parts were enclosed within a
metal cabinet. Respondent points out that §1910.145(f)(3) does not require tags where guarding
is in place, the metal cabinet enclosing S4 satisfied that requirement. It notes that in the Federal
Register document adopting many of the current rules under Subpart S, it states at 59 FR 4320,
4419 n.95 that “an employee is isolated from an energized part if the installation prevents the
employee from coming within the withstand distance for the voltage required.” The regulations
also define “guarded” as “Covered, fenced, enclosed or otherwise protected, by means of suitable
covers or casings, …designed to minimize the possibility, under normal conditions, of dangerous
approach or accidental contact by persons or objects.” 29 CFR 1910.269(x). That section also
defines a “barrier” as “A physical obstruction which is intended to prevent contact with
energized lines or equipment or to prevent unauthorized access to a work area.”
Section 1910.269(u)(4)(i)(C)(1) recognizes enclosing live parts “within grounded metal-
enclosed equipment” as a means of guarding to allow even unqualified persons to enter a
transmission, distribution, or transformation facility, as required by 1910.145.” Id. (Emphasis

                                             33

added)
A warning sign was already present on the door of S4 at all times of the alleged violation.
Presence of similar signs is not relevant. Thus, the Secretary failed to show that respondent was
obligated to place additional tags on S4.
Finally, respondent contends that OSHA cannot cite 1910.145(f)(3) as a stand-alone
violation. OSHA has noted that the “Standard does not contain requirements for employers to
post signs and tags. Instead, other OSHA standards in Part 1910 directly specify the posting
requirements for the signs and tags described by this Standard.” 66 FR 21414 at 21414 (2001)
Thus, according to OSHA‟s own interpretation, 1910.145(f)(3) did not impose any requirements
that tags be posted.
Discussion

For reasons given earlier, I find that the originally cited standard, 29 C.F.R. §1910.335(b)(1)
was not applicable to the work being performed by the Vault Room crew. Respondent also argues
that the alternative standard, 29 C.F.R. §1910.145(f)(3), does not apply on the grounds that it is
does not impose any substantive requirements. In support it cites to 66 FR 21414 (April 30,
2001). That publication concerned “the collection-of-information requirements of the standard on
“Specifications for Accident Prevention Signs and Tags” in regards to its proposal to decrease the
existing burden-hour estimates of OMB‟s collection-of-information requirements. Justifying its
removal of the burden hours previously attributed to the standard, OSHA stated:
The Agency notes that the Standard does not contain requirements for
employers to post signs and tags. Instead, other OSHA standards in part 1910
directly specify the posting requirements for the signs and tags described by this
Standard.

However, the Notice also stated that:
OSHA is recognizing an additional paperwork requirement that it previously
overlooked. The Standard requires employers to select signs and tags that are
appropriate to the dangers and hazards identified in the workplace; paragraphs
(c)(1)(i), (c)(2)(i), (c)(3), (e)(4), (f)(3), (f)(5) through (f)(7), and (f)(8)(i) specify
the signs and tags that employers must select for these dangers and hazards. In
addition, paragraphs (d)(l) through (d)(10), (e)(2), (f)(4)(i) through (f)(4)(iv),
(f)(7), and (f)(8)(ii) provide the design and wording requirements for these signs
and tags. Therefore, employers must ensure that the signs and tags selected are
appropriate for the identified dangers and hazards and meet the design and
wording requirements of the Standard.

                                                 34

Id.
Where the meaning of a standard is vague, the Commission is obligated to defer to the
Secretary‟s reasonable interpretation. Martin v. OSHRC (CF&I), 499 U.S. 144, 150 (1991).
The Federal Register section cited by respondent merely has to do with paperwork requirements
and is not intended to be a formal interpretation of the substantive requirements of the standard.
Also, the notice makes it clear, that (f)(3) applies and requires that employers “ensure that the
signs and tags selected are appropriate for the identified hazards.” Clearly, as noted, the
Secretary is alleging that the universal signs on all the cabinets failed to achieve the goal of the
standard, which is to differentiate live energized parts from de-energized parts. Accordingly, I
find the Secretary‟s interpretation to be reasonable and I find the standard applicable to the
alleged hazardous condition.
In its opening brief, at p.1, O‟Connell sets forth stipulations taken from the parties‟ Joint
Pre-Hearing Statement. The following stipulations are of relevance here:
Stipulation #30: O‟Connell Electric did not install any special signs to
remind its employees that two electrical switches (the „25B‟ switches) remained
energized. All four switches did have pre-existing signs that read „DANGER
HIGH VOLTAGE.‟
Stipulation #31: O‟Connell Electric did not install any special tags to
remind its employees that two electrical switches remained energized.
Stipulation #32: O‟Connell Electric did not erect any barricades to limit
access to the two electrical switches that remained energized.
Stipulation #33: O‟Connell Electric did not utilize an attendant to remind
its employees that two electrical switches remained energized.

   These stipulations seem to indicate that there was nothing to distinguish the four cabinets.

O‟Connell argues that the warning signs on all four switch cabinets were sufficient to satisfy the
standard. However, the clear intent of the standard is to “prevent accidental injury” from
hazardous conditions that are “unexpected or not readily apparent.” The purpose of this standard
is not satisfied where the posted signs fail to distinguish between the hazardous energized
cabinets from those that are de-energized. Similarly, the purpose of the standard is not satisfied
where the guarding provided fails to distinguish between hazardous and nonhazardous
installations and, therefore, fails to provide a “positive means of protection.”
However, despite the stipulations, the evidence clearly demonstrates that Schoenfeld
placed a lock and tag on all four cabinets and that he removed the lock and tags from cabinets S2

                                              35

and S3 to enable the work, while leaving them on cabinets S1 and S4. While this evidence is not
inconsistent with stipulations #30, 32 and 33, it does appear to conflict with stipulation #31,
which states that no special tags were placed on cabinets S1 and S4 to remind employees that the
two remaining switches remained energized. This apparently conflicting evidence is easily
reconciled. The locks and tags were placed on all four cabinets and only removed from switches
S2 and S4 to enable the crew to do their work. Having been originally placed on all the cabinets,
Stipulation #31 is accurate, insofar as no “special tags” were placed on switch cabinets S1 and
S4. Also, the stipulation says nothing about locks and there is no dispute between the parties that
cabinets S1 and S4 were locked.
Nonetheless, the Secretary asserts that O‟Connell should have either placed signs specific
to cabinets S1 and S4, warning employees that they were energized, or placed some sort of tape
or other physical barrier to warn employees or prevent access. However, while work was
proceeding on S2 and S3, that they were unlocked and open should have provided sufficient
notice to the crew as to which cabinets they were to work upon. As noted, supra, the Vault
Room crew was a highly trained, experienced, and competent group of electricians. They were
fully briefed on the scope of their work. Although after work was completed, the grounds were
removed and the cabinet locked, there is no evidence that Schoenthal‟s tags were replaced on the
doors. The two energized cabinets, on the other hand, were locked and tagged. Furthermore, after
work was completed on S2 and S3, there is no evidence to suggest why any employee would
have cause to enter any of the four cabinets after the grounds were removed and the cabinets S2
and S3 were locked. On this evidence, I find that there were adequate identifiers to inform the
employees not to enter cabinets S1 and S4. The Secretary also asserts that a barricade or even
yellow warning tape would have adequately warned the employees of the hazards presented by
cabinets S1 and S4. Certainly, as O‟Connell points out, a lock on a cabinet is a form of barricade.
There is nothing in the record to suggest that an employee would not be just as likely to ignore
yellow tape as he would a locked or tagged door. Accordingly, the item is vacated.

IV. Lockout/Tagout (“LOTO”)
A. Facts
The next two items allege violations of Lockout/Tagout (“LOTO”). As noted, each of the
switch cabinets in the Vault Room were secured by a Yale lock and key (Tr. 358). Additionally,

                                             36

the key opened the transformer cabinets in the Vault Room (Tr. 327). Schoenthal chose to secure
the key in a group lockbox (Tr. 317). Under the group lockbox procedure, the key was placed in
a box and all crew members from both rooms were supposed to place their personal lock on the
group box. This would ensure that the Yale key could not be removed until all crew members
first removed their locks (Tr. 54, 107, 330). However, the evidence indicates that not all of the
employees placed their personal locks on the group lockbox, including employees from the
Adjacent Room (Tr. 55, 68, 138, 164, 263). Some employees had to get the key to do work on
the switch and did not later replace the key (Tr. 55). Sometime after the safety meeting on May
16, Schoenthal removed the Yale key from the lockbox and gave it to a member of the Vault
Room crew. It remained out of the lockbox for the remainder of the shift, until the accident
occurred (Tr. 333). Several employees interviewed by the CO indicated that they were not sure
how the group lockbox procedure worked (Tr. 132).
Schoenthal also indicated that he considered the lockbox policy to be only optional and that,
instead, he used a mandatory sign-in/sign-out sheet where no equipment could be re-energized
until all employees were accounted for by their signing out on the sheet (Tr. 68, 128, 328).
Both items involve conditions in the Adjacent Room. In the Adjacent Room, the bus ducts
were hung high on the ceiling and the crew could plainly see that they were physically
disconnected from the switch gear (Tr. 154-155). These bus ducts remained disconnected from
all power sources at all times during the shift (Tr. 141, 171). This physical disconnection from
the power sources left no way for the equipment in the Adjacent Room to which employees had
access from being energized.
Item 11
Item 11 alleges that O‟Connell violated 29 C.F.R. §1926.21(b)(2) which provides:
1926.21 Safety training and education.
* * *
(b) Employer responsibility.
* * *
(2) The employer shall instruct each employee in the recognition and
avoidance of unsafe conditions and the regulations applicable to his
work environment to control or eliminate any hazards or other exposure
to illness or injury.

   Specifically, the citation alleges that in the Adjacent Room:
   Employees were removing and replacing switchgear, including conduit & wiring,

                                             37

and dismantling busses and hooking them back up. The employer had written
Lockout & Tagging procedures which was the company‟s procedure to render
circuits inoperative when performing construction as well as general industry type
work. They used these procedures to protect their employees from the hazard of
exposure to electric parts that might unexpectedly become energized. It was
determined that six switches needed to be opened and locked out to protect the
above employees. These switches were opened and locked out and the foreman
placed his lock & tag on a hasp that was attached through the handle of each of
the six switches. In lieu of requiring each employee performing the work to also
put their individual lock & tag on the hasp attached to each of the six switches, a
group lockout box was used. The 6 keys to the foreman‟s locks were placed inside
the box. Then, each of the employees performing the work is to put their
individual lock on the outside of the group lockout box so that the foreman‟s keys
cannot be removed until each worker‟s lock has been removed from the box.
Employees were not trained about the company‟s Lockout/Tagout program
requirement that each of the employees performing the work is to put their
individual lock on the outside of the group lockout box so that the foreman‟s‟ keys
cannot be removed until each worker‟s lock has been removed from the box.

                                          Arguments
   Secretary

The Secretary contends that O‟Connell was aware of the electrical hazards at the jobsite and
introduced the group lockbox to abate them. Yet, O‟Connell‟s employees demonstrated
substantial confusion regarding how a group lockbox procedure operates. Indeed, Schoenthal
himself violated the concept by not requiring all employees to attach their locks and by removing
the Yale key and placing it in the custody of an employee.
Respondent
Respondent asserts that LOTO was not applicable to the Adjacent Room crew because it
contained no electrical hazards. It points out that each of the busses that could carry power to the
equipment in the Adjacent Room had been disconnected and disassembled. Because of the
physical disconnection of the power sources there was no way for the equipment to become
energized. Therefore, O‟Connell takes the position that LOTO procedures were not applicable to
the Adjacent Room.
Discussion
The gravamen of a violation of 29 C.F.R. §1926.21(b)(2) is that O‟Connell failed to
instruct “its employees about the hazards they may encounter on the job and the regulations
applicable to those hazards.” Concrete Construction Co., 15 BNA OSHC 1614, 1619 (No. 89-

                                             38

2019, 1992). To fall within the standard requires that this failure to instruct (1) created an unsafe
condition and (2) resulted in the employees‟ inability to comply with applicable regulations. The
Secretary‟s theory for this item is that the alleged confusion surrounding the group lock box
demonstrated that O‟Connell failed to instruct its employees in the necessity and proper use of a
group lock box procedure and exposed the employees in the Adjacent Room to the hazard of
accidental energization.
The evidence fails to demonstrate the need for any LOTO procedure in the Adjacent
Room. Before the Adjacent Room crew arrived, Schoenthal had the equipment tested and
grounded and the bus ducts separated from the equipment they were to work on (Tr. 344).
Indeed, the busses were not only visibly disconnected (Tr. 154-155), but also they were hanging
from the ceiling where they were out of reach. Thus, the potential electrical hazards were
eliminated (Tr. 344). The citation claimed that Schoenthal put his lock on the hasp on all six
switches. The evidence demonstrates that those six pieces of electrical equipment involved the
four cabinets and two transformers in the Vault Room (Tr. 22, 42, 53, 54, 69). The Secretary‟s
concern is that the accidental energization of equipment in the Vault Room would endanger
employees in the Adjacent Room. However, the record fails to demonstrate that the Adjacent
Room crew would have been exposed to any hazard by the accidental energization of equipment
in the Vault Room.
The disassembly of the busses to the switches in the Adjacent Room was scheduled to
continue for the rest of the day, until the Adjacent Room crew replaced the switching equipment
in the room. This required that, among other steps, new switches be installed and attached to the
busses. Until that occurred, there was no threat of accidental energization. Simply put, there was
nothing to energize. The busses, which would have received energy from any accidental Vault
Room energization were hanging from the ceiling and completely disconnected from the
switches. This was not the typical LOTO situation where equipment is de-energized by tripping a
switch, which needs to be locked out or tagged so that the switch cannot accidentally be turned
back on. Here, there was no switch, dial, lever, etc. capable of energizing the equipment. Rather,
the Adjacent Room switches were totally disconnected from any electrical source and would
remain that way until reconnected when the Adjacent Room Crew finished their work (Tr. 154-
155). Respondent had a mandatory sign in/sign out sheet which it was using to ensure that all
employees were accounted for and clear before they eventually re-connected and re-energized

                                             39

the switches in the Adjacent Room.
If there was a hazard in the Adjacent Room, it was the possibility for feedback. However,
that is the purpose of grounding, and does not require LOTO. Until the switches were replaced
and the busses reattached, there was no risk of unexpected energization that could be addressed
by LOTO. The Commission has held that LOTO applies only when there is a hazard of
“unexpected” energization. General Motors Corp., 17 BNA OSHC 1217 (No. 91-2973,
1995)(consolidated), aff ’d 89 F.3d (6th Cir. 1996). Here there was no such hazard.
As O‟Connell points out, the CO apparently did not fully comprehend that there was no
hazard of unexpected energization (Tr. 100-101) and that the failure to properly instruct the
employees in the group lock box procedure did not result in a failure to instruct employees in the
recognition and avoidance of any unsafe condition or regulation applicable to their work
environment. Accordingly, the item is vacated.
Item 12
Item 12 alleges that O‟Connell failed to comply with 29 C.F.R. §1926.417(b) which
provides:
1926.417 Lockout and tagging of circuits.
* * *
(b) Equipment and circuits. Equipment or circuits that are de-energized shall be rendered
inoperative and shall have tags attached at all points where such equipment or circuits can
be energized.

As amended the citation specifies that in the Adjacent Room:
Employees were removing and replacing switchgear, including conduit and
wiring and dismantling busses and hooking them back up. The employer had
written lockout/tagout procedures which were intended to render circuits
inoperative when performing construction and general industry assignments thus,
protecting employees form [sic] the hazards of exposure to electrical parts which
may become unexpectedly energized. It was determined that six switches needed
to be locked and tagged out. The foreman locked and tagged out the switches, by
placing his locks and tags on hasps which were attached to handles of each of the
six switches. Instead, the foreman created a group lock box. He then placed his
six keys in the group lock box. The other employees were then supposed to place
their individual locks and tags on the outside of the group lock box so that the
foreman‟s keys could not be removed from the lock box unless all of the
individual locks and tags were removed. Some employees did not put their
individual locks and tags on the group lock box as required.

                                             40

Arguments
Secretary
The Secretary argues that the assertion of respondent‟s expert, Strang, that no hazard
existed after equipment was locked out and grounded is not supported by the evidence. Adjacent
Room crewman, Bacon, indicated concern about potential electrical back feeds from another part
of the building travelling into and affecting equipment in the Adjacent Room (Tr. 137). Also,
Adjacent Room crewmember Reynolds testified that there was a potential electrocution hazard
once they started to reconnect equipment in the Vault Room (Tr. 160). At least one and possibly
two employees failed to put their locks on the group lock box. Any crewmember could have
retrieved keys from the box and re-energized equipment.
Also, respondent grounded the bus ducts that ran from the Vault Room to the Adjacent
Room so they would not transmit electricity to the Adjacent Room when that crew was
reconnecting the metal clad switchgear (Tr. 38-39, 51-52, 152, 157, 161, 204-206, 318-319).
There was a potential for electrocution to the Adjacent Room crew if the bus ducts were not
grounded (Tr. 152, 158-159).
The Secretary also points out that O‟Connell locked out the 1600 amp feed from O‟Brian
Hall to Baldy Hall because it presented an electrocution hazard to the Adjacent Room crew (Tr.
38-39, Ex. P-23, p. 12 para. 2).

      Respondent
      Respondent contends that the Secretary failed to show that the standard was violated or

that any employee was exposed to a hazard. It argues that employees in the Adjacent Room were
not exposed to any electrical hazard because all sources of electrical power were physically
disconnected. As discussed supra, there were no points where any of the equipment in the
Adjacent Room could be energized because all sources of power, namely the three busses that
fed the Adjacent Room switchgear had been physically disconnected from that switchgear.
Because there was no source of power to be locked out, employees were not exposed to any
hazard.
O‟Connell also points out that §1926.417(b) requires that “Equipment or circuits that are
de-energized shall be rendered inoperative and shall have tags attached to all points where such
equipment or circuits can be energized.” By disconnecting and making inaccessible all the
41
sources of power (busses), the Adjacent Room switchgear was rendered inoperative. There were
no points where the switchgear could be energized. Thus, disconnection of the busses satisfied
all the requirements of the standard.
Respondent points out that it was using a mandatory sign-in/sign-out sheet. Therefore,
before power was restored, everybody had to sign the sheet establishing that they were out of the
room and all their gear removed. This provided the requisite protection to employees
Discussion
The duty imposed by the standard is clear: de-energized circuits shall be rendered
inoperative and shall have tags attached to all points where such equipment or circuits can be
energized.
The evidence establishes that the de-energized circuits in the Adjacent Room were
rendered inoperative. The busses that fed the Adjacent Room had been physically disconnected
from that switchgear and hanging from the ceiling (Tr. 155, 171). Therefore, the switchgear was
de-energized and would remain that way until they were reattached to busses at some point in the
future (Tr. 201-202, 204, 319). Moreover, all the electrical equipment in the Adjacent Room was
grounded. (Tr.156). The evidence fails to suggest any way, other than the replacement and
reconnection of the busses, where the equipment could be energized. There simply were no
points where the equipment could be re-energized. Accordingly, the evidence fails to
demonstrate that attaching tags would have reduced or eliminated any hazard of accidental
energization.
Nonetheless, the Secretary argues crewmember Bacon expressed concern about potential
electrical back feeds from another part of the building travelling into and affecting equipment in
the Adjacent Room (Tr. 137). Foreman Schoenthal testified, however, that the concern was that
there might be feedback coming into the Adjacent Room from the 480-volt breaker in O‟Brian
Hall. That breaker was locked out independently of the group lockbox procedure (Tr. 318). The
Secretary also argues that Adjacent Room crew member Reynolds testified there was a potential
electrocution hazard once they started to reconnect equipment in the Vault Room (Tr. 160).
However, that testimony presupposed that the busses in the Adjacent Room were already
reconnected to the replaced switch gear. That was not a work activity scheduled for that day.
Moreover, before that re-energization could occur, each employee was required to sign out on the
mandatory sign-in/sign-out sheet to guarantee that they were clear of danger.

                                            42

Accordingly, I find that the Secretary failed to establish a violation of 29 C.F.R.
§1926.417(b) and the item is vacated.

V. Hazard Assessment
Item 3
Item 3 alleges that O‟Connell failed to complete a certificate of hazard assessment for
employees scheduled to perform electrical work in both the Vault Room and the Adjacent Room
as required by 29 C.F.R. §1910.132(d)(2). The cited standard provides:
1910.132 General requirements.
* * *
(d) Hazard assessment and equipment selection.
* * *
(2) The employer shall verify that the required workplace hazard
assessment has been performed through a written certification that
identifies the workplace evaluated; the person certifying that the
evaluation has been performed; the date(s) of the hazard assessment;
and, which identifies the document as a certification of hazard
assessment.

                              Facts
   According to the CO, Foreman Schoenthal told him that although he conducted a hazard

assessment, he did not prepare a Certificate of Hazard Assessment (Tr. 62-63). Respondent‟s
expert, Douglas Strang, testified that the safety meeting sheet and the location safety sheet (Ex.
2) completed by Schoenthal together formed a Certificate of Hazard Assessment (Tr. 404, Ex. R-
34). Strang pointed out that the location safety sheet and the safety meeting sheet together
showed that the site had been reviewed, who was going to be in charge, emergency numbers,
sign in forms, and a procedure check-off (Tr. 432).

                                  Arguments
   Respondent:

   O‟Connell points out that the Secretary does not allege that it failed to perform a hazard

assessment. Rather, the Secretary alleges only that the paperwork it did complete failed to
comply with the technical requirements of the standard. O‟Connell argues that it completed a
Location Safety Sheet that served as a de facto certification of hazard assessment.
Further, even if there was a technical violation, the Secretary failed to demonstrate that

                                            43

this paperwork violation created a substantial probability that death or serious physical harm
could result. Therefore, if affirmed, the violation should be classified as other than serious or de
minimis.
Secretary:
The Secretary points out that Schoenthal admitted that he did not complete a written
certificate of hazard assessment. She contends that O‟Connell‟s contention that its Location
Safety Sheet is a de facto certification is not supported by the record.

                                   Discussion

The standard requires the employer to prepare a document entitled “Certification of Hazard
Assessment.” The evidence is undisputed that O‟Connell did not prepare such a document.
Furthermore, I find that the record does not support O‟Connell‟s assertion that the Location
Safety Sheet together with the safety meeting sheet constituted an acceptable substitute.
First, the Location Safety Sheet contains no certification that the evaluation was performed.
Also, the only date on the Location Safety Sheet is May 15, 2009, and makes no mention of May
16, the date of the accident or the nature of the work scheduled for that day. Also, the sheet
identifies no hazards. It identifies “Backup Emergency Generators” as a possible source of
feedback; identifies “O‟Brian Feeder, Baldy Hall Feeder 25B & 53A” as Lockout/Tagout/Ground
Locations,” and as “Identified Hazards” merely says “all areas to be tested and personal grounds
installed at each location. The[re] will be heavy traffic area.” (Ex. P-12). Similarly, the Safety
Meeting Sheet does not identify or assess any hazards. Rather, it only contains a check list of
topics to be covered, using such terms as “Discuss,” “Review,” and “Explain.” (Ex. P-11).
Indeed, respondent‟s safety expert testified that he has never before seen a Location Safety Sheet
and a Safety Meeting Sheet used as a Certificate of Hazard Assessment (Tr. 404-405).
There really is no dispute that there was, at a minimum, a technical violation of the
standard. The standard requires that the document be identified as a “certification of hazard
assessment.” Although the Secretary does not dispute that an assessment was made, respondent
failed to prepare a document formally called a “Hazard Assessment”, and there was no
certification that such an assessment was made.
A violation is de minimis when a deviation from the standard has no "direct or
immediate" relationship to employee safety. Dover Elevator Co., 15 BNA OSHC 1378, 1382

                                              44

(No. 88-2642, 1991). Requiring that there be a certification creates accountability and therefore
increases the likelihood that a proper assessment will be made. Therefore the failure to have the
document is not de minimis.
The Secretary asserts that the violation was serious. However, the Secretary adduced no
evidence that the violation was likely to result in death or serious physical harm. I find that,
because an assessment was made and the hazards covered by Schoenthal during the morning
safety meetings, it was unlikely that the result of the violation would be death or serious physical
harm. According, the item is affirmed as other than serious.
As noted under items 2 and 5, supra, the Secretary proposed a penalty of $6300 for this
violation. While the Secretary properly considered the statutory factors set forth in section 17(j)
of the Act, the proposed penalty was based on the assumption that the violation was serious.
Having found the violation to be other than serious, however, requires a substantial reduction in
the penalty. Considering the gravity of the violation and the 17(j) factors, as developed at the
hearing, I find that a penalty of $630 is appropriate.

                                   ORDER
    Based upon the foregoing findings of fact and conclusions of law, it is ORDERED that:

(1) Citation 1, item 2 alleging a serious violation of 29 CFR §1910.132(d)(1)(ii) is AFFIRMED
and a penalty of $6300 is ASSESSED;
(2) Citation 1, item 3 alleging a serious violation of 29 C.F.R. §1910.132(d)(2) is AFFIRMED;
as other than serious and a penalty of $630 is ASSESSED;
(3) Citation 1, item 4(b) alleging a serious violation of 29 C.F.R. §1910.269(l)(2) is VACATED;
(4) Citation 1, item 5, alleging a serious violation of 29 C.F.R. §1910.138(a) is AFFIRMED and
a penalty of $6300 is ASSESSED;
(5) Citation 1, item 8, alleging a serious violation of 29 C.F.R. §1910.133(a)(1) is VACATED;
(6) Citation 1, item 11 alleging a serious violation of 29 C.F.R. §1926.21(b)(2) is VACATED;
(7) Citation 1, item 12, alleging a serious violation of 29 CFR §1926.417(b) is VACATED;
(8) Citation 1, item 13, alleging a serious violation of 29 CFR §1910.145(f)(3) is VACATED.

                                             45

SO ORDERED.

                           _____/s/_________________________
                           The Honorable John H. Schumacher
                                  U.S. OSHRC Judge

Dated: June 14, 2011
Washington, D.C.

                      46

Get today's answer for your situation

You just read what one judge decided for one employer in 2011, and it binds only those parties. Ezel checks the current OSHA standards and Commission precedent and answers your specific situation, with citations.

Opens in Ezel Pro. Every answer cites the authority it relies on.